www.glendimplex.de 452167.66.02 · FD 9509
EN-10
English
LSA 60TUR
12 Device information
1
Type and order code
LSA 60TUR
2
Design
Heat source
Air & brine
2.1
Model
Reversible with mode for two heat sources
2.2
Controller
WPM wall-mounted
2.3
Thermal energy metering
no
2.4
Installation location
Outdoors
2.5
Performance level
2
3
Operating limits
3.1
Heating water flow / return
°C
up to 60
1
±2 / from 18
Cooling water flow
°C
+6
2
to +20
Air (heating)
°C
-20 to +40
Air (cooling)
°C
+15 to +45
Brine (heating)
°C
+5
flow
to +25
return
4
Flow / sound
4.1
Heating water flow rate / internal pressure differential
in accordance with 14511
A7/W35-30
m³/h / Pa
10.5 / 6500
A7/W45-40
m³/h / Pa
10.2 / 6200
A7/W55-47
m³/h / Pa
6.2 / 2300
minimum
m³/h / Pa
5.3 / 1700
4.2
Minimum cooling water throughput /internal pressure differential
3
m³/h / Pa
10.8 / 6900
4.3
Brine flow rate / internal pressure differential
m³/h / Pa
11.0 / 32500
4.4
Sound power level according to EN 12102Normal mode / lowered operationdB(A)
up to 74 / up to 70
4.5
Sound pressure level at a distance of 10 m (air outlet side)
4
Normal operation / reduced operation
dB(A)
up to 45 / up to 41
4.6
Air flow (controlling range EC fan)
m³/h
10000 - 22000
5
Dimensions, weight and filling quantities
5.1
Device dimensions
5
H x W x L mm
2300 x 2110 x 1000
5.2
Weight of the transportable unit(s) incl. packaging
kg
1090
5.3
Device connections for heating
inches
R 2"
5.4
Device connections for brine
inches
R 2"
5.5
Refrigerant / total filling weight
type / kg
R417A / 33.0
5.6
Lubricant / total filling quantity
type / litres
Polyolester (POE)/7.2
5.7
Volume of heating (cooling) water in device
water / brinelitres
18.8 / 12.0
6
Electrical connection
6.1
Supply voltage / fuse protection
3~/PE 400V (50Hz) / C50A
6.2
Control voltage / fusing via WPM
1~/N/PE 230V (50Hz) / 4 ET
6.3
FI circuit breaker / category
Yes / A
6.4
Degree of protection according to EN 60 529
IP 24
6.5
Starting current limiter
Soft starter
6.6
Rotary field monitoring
No
6.7
Starting current
A
78
6.8
Nominal power consumption A7/W35 / max. consumption
6
kW
14.75 / 29.9
6.9
Nominal current A7/W35 / cos
A / ---
28.8 / 0.8
6.10 Power consumption of compressor protection (per compressor)
W
70, thermostatically controlled
6.11 Power consumption of fan
kW
up to 3.1
7
Complies with the European safety regulations
7
8
Additional model features
8.1
Type of defrosting
Reverse circulation
8.2
Condensate tray frost protection / Water in device is protected from freezing
8
Ja
8.3
max. operating overpressure (heat source / heat sink)
bar
3.0
8.4
Hydraulic 4-way reversing valve (external)
Accessories (recommended)