EN-9 452167.66.02 · FD 9509
www.glendimplex.de
English
LSA 60TUR
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the system.
Acids must be used with care and the regulations of the employ-
ers liability insurance associations must be adhered to.
The instructions of the cleaning agent manufacturer must always
be observed.
9.3 Cleaning the air system
The evaporator, fan and condensate drain should be cleaned of
contamination (leaves, twigs, etc.) before each new heating pe-
riod.
ATTENTION!
Before opening the device, ensure that all circuits are disconnected from
the power supply.
To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects when cleaning.
Under extreme weather conditions (e.g. snow drifts), ice forma-
tion may occur on the air intake and air outlet grids. If this hap-
pens, the ice must be removed from the vicinity of the intake and
air outlet area to ensure that the minimum air flow is maintained.
To ensure proper drainage from the condensate tray, it must be
regularly inspected and cleaned, if necessary.
All panelling can be removed to allow accessing the inside of the
device.
The two sash fasteners must be opened for this purpose. The
cover must then be slightly tilted forward and lifted off toward the
top.
The upper panels are hooked into the cover panel. To dismantle,
open the two fasteners and unhook the panels by pulling them
back.
9.4 Maintenance
Refrigeration circuits with a minimum refrigerant fill quantity of 30
kg must be tested for leaks every six months by the operator ac-
cording to regulation (EC) No. 842/2006.
The leakage tightness test must be documented and archived for
a minimum of 5 years. The test is to be carried out by certified
personnel only, according to regulation (EC) No. 1516/2007.
The table enclosed in the attachment can be used as a basis for
the documentation.
NOTE
Local regulations may differ from EU directive 842/2006. The appropriate
local regulations for the heat pump leakage tightness test must be
observed.
10 Faults / troubleshooting
This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be in-
dicated on the heat pump manager display. In this case, consult
the "Faults and troubleshooting" page in the operating instruc-
tions of the heat pump manager. If you cannot correct the fault
yourself, please contact your after-sales service technician.
ATTENTION!
Work on the heat pump must only be performed by authorised and
qualified after-sales service technicians.
11 Decommissioning /
disposal
Before removing the heat pump, disconnect it from the power
source and close all valves. The heat pump must be dismantled
by trained personnel. Observe all environmental requirements
regarding the recovery, recycling and disposal of materials and
components in accordance with all applicable standards. Partic-
ular attention should be paid to the proper disposal of refrigerants
and refrigerant oils.
Opening the lower covers
Closing the lower covers
2
3
1
1
3
2
1
1
1
1
3
1
2
3
1
2
Opening the upper cover panels
Closing the upper cover panels
2
2
3
1
1
2
1
1
3