Routine Testing and Maintenance 

 

Routine Testing (recommended weekly in co-ordination with the weekly fire alarm test) 

As the Xvent is a safety critical product it is anticipated that it will be subject to a regular testing regime. This is the reason why, 
following fire activation, it has been made necessary to close the Xvent manually using the wall mounted control switch. In this way 
it is possible to walk to each Xvent in the building, confirm that it has opened to the fire open position, and then check that the Xvent 
closes with no faults present (i.e. green status light on wall mounted control switch). 
 

General Maintenance and Safety 

To keep the Xvent in good working order there are a few basic points that should be observed: 

 

Do not place anything on, or cause obstruction to the moving section of the product when opening the unit as this may 

cause damage to the unit’s mechanisms an

d/or prevent it from opening. 

 

Do not walk or sit on the unit. 

 

Make sure that fingers and other obstructions are clear of the product and its mechanisms during any operation, severe 
damage/injury may be caused. 

 

Do not touch the motors/mechanisms after operating the unit as they may become hot. 

 

Do not remove the treadplate protecting the control board, as this may allow the controls to become damaged. 

 

Do  not  allow  unauthorised persons  (e.g. children)  to  operate the product  as  this  may  lead  to  injury or  damage  to  the 
product. 

 

Specific Maintenance Requirements  

The Xvent is a safety critical product and maintenance  must only be carried out by suitably qualified personnel*. The following 
maintenance requirements must be completed and logged on the sheets at the back of this manual. Glazing Vision can offer a 
service/maintenance contract 

 please contact us for further details. 

 
*Suitably  qualified  assumes  Glazing  Vision  Engineers  or  Approved  Installers  (installers  that  have  attended  a  Glazing  Vision 

Installation training course for this product and carry ‘Approved Installer’ status),

 or an  experienced electro-mechanical service 

engineer. 
 

Monthly Requirements 

 

The product should be fully opened and closed to ensure that the seals are free, and the mechanisms function evenly. 

 

Annual Requirements (at least annual - recommended every 6 months) 

 

Check the integrity of the glazing unit (there should not be any misting or condensation). 

 

Check that all moving parts are free from debris. 

 

Grease (Shell Gadus s2 v220 2 or equivalent) the mechanism leadscrews. 

 

Lubricate (WD-40 Specialist High Performance Silicone Lubricant or equivalent) all other moving parts and check they move 
freely. 

 

Check that all mechanism arms are straight and true. 

 

Check that all fixings are appropriately tightened. 

 

Check that access to the overrides is clear and advise the relevant party to amend if not. 

 

Check all electrical cables and ensure that they are not trapped and/or damaged. 

 

Check that no water is in the unit. 

 

Clean and inspect all rubber/silicone seals, contact Glazing Vision to arrange for replacement seals to be fitted if required. 

 

Check that the battery terminals are crimped correctly. 

 

Check that electrical connections are well made and secure. 

 

Check that the control switch does not show any errors. 

 

Test the ventilation operation. 

 

Test the fire operation on mains power. 

 

Test the fire operation without mains power (just with battery backup). 

 

While testing without mains power check that 

the “

no mains power

 warning is active. 

 

Test any optional extras present. 

 

Every 5 Years 

 

Replace the back-up batteries. 

 
 

Summary of Contents for Xvent

Page 1: ...405 OM UK 001 v1 0 09 Jul 2020 www glazingvision co uk 44 0 1379 658300 info glazingvision co uk Xvent...

Page 2: ...tion Page Introduction 3 Safety Information 4 Basic Operation 6 Controls and Operation 7 Manual Override 9 Troubleshooting 12 Glass Specification and Breakage Instructions 13 Routine Testing and Maint...

Page 3: ...access A variety of optional extras including a rain sensor thermostat remote control and Building Management System connectivity are available This product is robust and long lasting boasting excelle...

Page 4: ...amage to the product and its mechanisms It should not be relied upon to prevent injuries Let our experts carry out your routine maintenance with a maintenance contract 44 0 1379 658300 info glazingvis...

Page 5: ...t may open close unexpectedly e g due to the rain sensor activating and cause injury Do not pull on the cables where they exit the product Doing so may loosen connections result in damage to the produ...

Page 6: ...arm activation must be by manual operation using the wall mounted control switch this is to allow somebody to walk around the building duringa fire drill and check each that each individual rooflight...

Page 7: ...ion releasing the switch stops the product in that position Note that the product will stop automatically when it becomes either fully open or closed Status Light The status light will illuminate gree...

Page 8: ...mote control together and immediately release them The status light on the remote control should turn red for a few seconds and then turn off If it turns green or amber try pressing the three buttons...

Page 9: ...support system in place unscrew the bolts using a pin torx driver This will disengage the mechanisms from the lid Next unscrew the mechanisms from the base frame and allowing them to be removed from...

Page 10: ...e legs from slipping when working take care not to knock the support legs out of place Figure 6 Support legs Support Option 3 Chain or Strap This option can be used when there is not enough space for...

Page 11: ...d by Glazing Vision personnel or Approved Installers If the manual override has been used the product requires re initialising As the Xvent is a safety critical product this will need to be done by a...

Page 12: ...n close button will clear this condition Continuous red after power on fault recovery Indicates that the product requires initialisation synchronisation Pressing close on the wall mounted switch will...

Page 13: ...eaning open the product and isolate the power supply then clean the rain sensor The thermostat if specified is reacting to a change in temperature and triggering the product to close Check that the th...

Page 14: ...ance requirements must be completed and logged on the sheets at the back of this manual Glazing Vision can offer a service maintenance contract please contact us for further details Suitably qualified...

Page 15: ...nsor if present Disposal at End of Life Glazing Vision design products with ease of recyclability at end of life in mind Many of the main components used are widely recyclable and we encourage you to...

Page 16: ...fied to BS EN 12101 2 2003 and is fully CE marked Visit our website or contact your technical sales advisor for up to date certification documentation The following label will be affixed to the exteri...

Page 17: ...ents yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement ye...

Page 18: ...cement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirement...

Reviews: