Glaziar Silence S20 User Manual Download Page 12

j) When the cylinders have been filled correctly and the process completed, 

make sure

that the cylinders and the equipment are removed from site promptly and 

all isolation valves on the equipment are closed off.

k)  Recovered  refrigerant  shall  not  be  charged  into  another  refrigeration 

system unless it has been cleaned and checked.

10 laBellInG

Equipment shall be labelled stating that it has been de-commissioned and 
emptied of refrigerant. The label shall be dated and signed.
Ensure  that  there  are  labels  on  the  equipment  stating  the  equipment 
contains flammable refrigerant.

11 recOVerY

When  removing  refrigerant  from  a  system,  either  for  servicing  or 
decommissioning,  it  is  recommended  good  practice  that  all  refrigerants 
are  removed  safely.  When  transferring  refrigerant  into  cylinders,  ensure 
that only appropriate refrigerant recovery cylinders are employed. Ensure 
that  the  correct  number  of  cylinders  for  holding  the  total  system  charge 
are  available.All  cylinders  to  be  used  are  designated  for  the  recovered 
refrigerant  and  labelled  for  that  refrigerant  (i.e.  special  cylinders  for  the 
recovery  of  refrigerant).  Cylinders  shall  be  complete  with  pressure  relief 
valve and associated shut-off valves in good working order. Empty recovery 
cylinders are evacuated and, if possible, cooled before recovery occurs.
The  recovery  equipment  shall  be  in  good  working  order  with  a  set  of 
instructions concerning the equipment that is at hand and shall be suitable 
for  the  recovery  of  flammable  refrigerants.In  addition,a  set  of  calibrated 
weighing scales shall be available and in good working order. Hoses shall 
be  complete with  leak-free  disconnect  couplings  and  in  good  condition. 
Before using the recovery machine, check that it is in satisfactory working 
order,  has  been  properly  maintained  and  that  any  associated  electrical 
components  are  sealed  to  prevent  ignition  in  the  event  of  a  refrigerant 
release. Consult manufacturer if in doubt. 
The recovered refrigerant shall be returned to the refrigerant supplier in the 
correct recovery cylinder,and the relevant Waste Transfer Note arranged. 
Do not mix refrigerants in recovery units and especially not in cylinders. 
If compressors or compressor oils are to be removed, ensure that they have 
been  evacuated  to  an  acceptable  level  to  make  certain  that  flammable 
refrigerant  does  not  remain within  the  lubricant. The  evacuation  process 
shall be carried out prior to returning the compressor to the suppliers. Only 
electric heating to the compressor body shall be employed to accelerate 
this process.When oil is drained from a system,it shall be carried out safely.

11

Summary of Contents for Silence S20

Page 1: ...Silence S20 S25 S30 S35 English www glaziar com User Manual...

Page 2: ...ontain an odour 5 Appliance shall be installed operated and stored in a room with a floor area larger than X m 2 X 4 for 5000 Btu h 7000 Btu h 8000Btu h X 7 7 for 9000Btu h 1000Btu h 10500Btu h WARNIN...

Page 3: ...ision of an individual specified in the use of flammable refrigerants 1 The appliance is for indoor use only 2 Do not use the unit on a socket under repairs or not installed properly 3 Do not use the...

Page 4: ...nsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can t...

Page 5: ...years and above and persons with reduced physical sen soty or mental capabilitie or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance...

Page 6: ...t needs to be repaired In case of breakdown turn off the unit only by the POWER button located on the control panel and contact your dealer If the supply cord is damaged it must be replaced by the man...

Page 7: ...procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 1 3 General work area All maintenance staff and others working in the local area shall...

Page 8: ...e and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerant...

Page 9: ...ands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmosphere...

Page 10: ...e system or isolated by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing proces...

Page 11: ...ce that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It...

Page 12: ...good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the...

Page 13: ...housing has no significant effect on the safety Nevertheless it is possible that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure i...

Page 14: ...on t cause any spark When brazing is required the following procedures shall be carried out in the right order Remove the refrigerant If the recovery is not required by national regulations drain the...

Page 15: ...should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant circuit with nitrogen for 5 min Evacuate...

Page 16: ...equipment using flammable refrigerants See national regulations Storage of equipment appliances The storage of equipment should be in accordance with the manufacturer s instructions Storage of packed...

Page 17: ...d the square clip at the other side 3 Attach the flat clip to the fitting opening at the back of the unit 4 Put the other side of the exhaust hose to the outside 5 Plug the power cord into the outlet...

Page 18: ...ool appears on the display Press TEMP or TEMP to adjust the temperature 16 C 31 C Press the SPEED button to adjust the fan speed 4 Dehumidifying mode Press the MODE button until the indicator light sh...

Page 19: ...rol 1 POWER Power on or off 2 MODE Press the button to select cooling dehumidifying or fan mode 3 TEMP Press the button to increase the temperature 4 TEMP Press the button to decrease the temperature...

Page 20: ...ir outlet and remove the filter 2 Wash the air filter by submersion into warm water about 40 C with neutral detergent rinse it under running water and dry it with a soft cloth 3 Install air filter car...

Page 21: ...isconnected or blocked The adjusted temperature is too high Air inlet is blocked by smth Close all windows and doors Remove the heat source Connect or clean exhaust hose Reset temperature adjustment s...

Page 22: ...ree replacement or repair will be excluded from the prior improper product manipulation Defects on parts and consumables as well as cleaning maintenance or replacement of said parts are therefore char...

Page 23: ...ocol and may thus contribute to global warming if it is released to the atmosphere Therefore only trained technicians with refrigerant certificate make a filling or emptying Your air conditioner does...

Reviews: