background image

8 cHarGInG PrOceDUres

In addition to conventional charging procedures,the following requirements 
shall be followed.
- Ensure that contamination of different refrigerants does not occur when 

using charging equipment. Hoses or lines shall be as short as possible to 
minimise the amount of refrigerant contained in them.

- Cylinders shall be kept upright.
-  Ensure  that  the  refrigeration  system  is  earthed  prior  to  charging  the 

system with refrigerant.

- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overfill the refrigeration system.
Prior  to  recharging  the  system  it  shall  be  pressure  tested  with  OFN. 
The  system  shall  be  leak  tested  on  completion  of  charging  but  prior  to 
commissioning. A follow up leak test shall be carried out prior to leaving 
the site.

9 DecOMMIssIOnInG

Before  carrying  out  this  procedure,  it  is  essential  that  the  technician  is 
completely familiar with the equipment and all its detail. It is recommended 
good  practice  that  all  refrigerants  are  recovered  safely.  Prior  to  the  task 
being  carried  out,  an  oil  and  refrigerant  sample  shall  be  taken  in  case 
analysis is required prior to re-use of reclaimed refrigerant. It is essential 
that electrical power is available before the task is commenced. 
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c)  Before  attempting  the  procedure  ensure  that  :mechanical  handling 

equipment is available, if required, for handling refrigerant cylinders; all 
personal  protective  equipment  is  available  and  being  used  correctly; 
the recovery process is supervised at all times by a competent person; 
recovery  equipment  and  cylinders conform to the appropriate standards.

d) Pump down refrigerant system,if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be 

removed from various parts of the system.

f) Make sure that cylinder is situated on the scales before recovery takes 

place.

g) Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i)  Do  not  exceed  the  maximum  working  pressure  of  the  cylinder,even 

temporarily.

10

Summary of Contents for Silence S20

Page 1: ...Silence S20 S25 S30 S35 English www glaziar com User Manual...

Page 2: ...ontain an odour 5 Appliance shall be installed operated and stored in a room with a floor area larger than X m 2 X 4 for 5000 Btu h 7000 Btu h 8000Btu h X 7 7 for 9000Btu h 1000Btu h 10500Btu h WARNIN...

Page 3: ...ision of an individual specified in the use of flammable refrigerants 1 The appliance is for indoor use only 2 Do not use the unit on a socket under repairs or not installed properly 3 Do not use the...

Page 4: ...nsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can t...

Page 5: ...years and above and persons with reduced physical sen soty or mental capabilitie or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance...

Page 6: ...t needs to be repaired In case of breakdown turn off the unit only by the POWER button located on the control panel and contact your dealer If the supply cord is damaged it must be replaced by the man...

Page 7: ...procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 1 3 General work area All maintenance staff and others working in the local area shall...

Page 8: ...e and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerant...

Page 9: ...ands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmosphere...

Page 10: ...e system or isolated by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing proces...

Page 11: ...ce that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It...

Page 12: ...good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the...

Page 13: ...housing has no significant effect on the safety Nevertheless it is possible that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure i...

Page 14: ...on t cause any spark When brazing is required the following procedures shall be carried out in the right order Remove the refrigerant If the recovery is not required by national regulations drain the...

Page 15: ...should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant circuit with nitrogen for 5 min Evacuate...

Page 16: ...equipment using flammable refrigerants See national regulations Storage of equipment appliances The storage of equipment should be in accordance with the manufacturer s instructions Storage of packed...

Page 17: ...d the square clip at the other side 3 Attach the flat clip to the fitting opening at the back of the unit 4 Put the other side of the exhaust hose to the outside 5 Plug the power cord into the outlet...

Page 18: ...ool appears on the display Press TEMP or TEMP to adjust the temperature 16 C 31 C Press the SPEED button to adjust the fan speed 4 Dehumidifying mode Press the MODE button until the indicator light sh...

Page 19: ...rol 1 POWER Power on or off 2 MODE Press the button to select cooling dehumidifying or fan mode 3 TEMP Press the button to increase the temperature 4 TEMP Press the button to decrease the temperature...

Page 20: ...ir outlet and remove the filter 2 Wash the air filter by submersion into warm water about 40 C with neutral detergent rinse it under running water and dry it with a soft cloth 3 Install air filter car...

Page 21: ...isconnected or blocked The adjusted temperature is too high Air inlet is blocked by smth Close all windows and doors Remove the heat source Connect or clean exhaust hose Reset temperature adjustment s...

Page 22: ...ree replacement or repair will be excluded from the prior improper product manipulation Defects on parts and consumables as well as cleaning maintenance or replacement of said parts are therefore char...

Page 23: ...ocol and may thus contribute to global warming if it is released to the atmosphere Therefore only trained technicians with refrigerant certificate make a filling or emptying Your air conditioner does...

Reviews: