GIRA
Info
Smoke detector plus / VdS
Instructions for Installation
Smoke detector plus / VdS
02/02
Seite: 6 von 6
Monthly
•
Press the test button;
–
If it emits the warning tone, the home smoke detector is in good working order.
–
If the warning tone is not emitted, please check the battery connection or replace the battery
with a new one. If the test results are then still negative, the home smoke detector must be
replaced.
6-monthly
•
Remove the home smoke detector from its base and wipe it with a damp cloth.
•
Reinsert the home smoke detector in its base and turn it clockwise until it clicks into place.
Technical data
Sensitivity
to prEN 12239 (95)
Operating voltage
9 V DC
Current consumption
Quiescent current
typical
Alarm current (type without relay)
max.25 mA
Alarm current (relay type)
max.50 mA
Relay module
NO contacts, volt-free
Switched voltage
max. 30 V DC
Switched current
max. 1 A
Battery rectangular
battery
Battery type
ICE6 LR 61, 9 V
Battery low power signal
1/min, 30 days
Alarm indicator
LED, red
Sounder
85 dB (A)
Ingress protection
IP 42
Ambient service temperature
+ 5 to + 40 °C
Storage temperature
- 5 to + 60 °C
VdS approval
see nameplate on smoke detector
Weight (without battery)
130 g
Acceptance of guarantee
We accept the guarantee in accordance with the corresponding legal provisions.
Please return the unit postage paid to our central service department giving a brief description
of the fault:
Gira
Giersiepen GmbH & Co. KG
Service Center
Dahlienstrasse 12
D-42477 Radevormwald
The CE sign is a free trade sign addressed exclusively to the authorities and does not include
any warranty of any properties.
Gira
Giersiepen GmbH & Co. KG
Postfach 1220
D-42461 Radevormwald
Telefon: +49 / 21 95 / 602 - 0
Telefax: +49 / 21 95 / 602 - 339
Internet: www.gira.de