TFD-1250 

Analogue Addressable Optical Smoke Detector 

Installation & Operating Guide 

Issue Date: 28/09/2017 

Rev:00 

 

Important Warnings 
General 

 

Before using the device read this manual carefully. Keep it just in case of necessity. 

 

Abide all the rules and precautions stated in the manual. Follow all the instructions one by one. 

 

Keep the devices away from water and moisture 

 

Conditions 

Do not energize the device above or below the given limits of extreme hot or cold conditions, 

Temperature

Between

 -

10°C and +55°C

 

Relative Humidity: 

%95 RH max

 

 
Service 

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. 

 
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical 

interventions have to be done by technicians of company. 

 
 

 
 

 
Malfunctions that require technical service 

In case of any malfunction or below conditions contact with your authorized service,  

 

When Mains cable or the plug is harmed,  

 

Contact of device with a fluid,  

 

Exposure of rain and water,  

 

Fell down of device or harmed outer cover,  

 

Serious performance fall on the device,  

 

Depending on the instructions stated in manual, if your device not working properly 

Contact with your authorized service in such terms.  

 

Maintenance on your own  

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any 

defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have 
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are 

allowed for cleaning 

 

Transportation 

Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions 

that caused by improper transportation is not under warranty. 

 

Human and Environmental Health 

 This device contains no chemical or biological elements that could harm human condition.  

 

 

 

 General Features

 

 

 

Advanced smoke detection algorithm that minimizes false alarms 

 

Rejection of transient signals that can be detected as alarms 

 

Adaptive intelligent protection by constantly sampling the environment 

 

Dust algorithm and warning to understand that it is getting polluted and unable to detect 

 

Easy to clean smoke chamber 

 

Ability to connect an remote indicator 

 

Two leds used for status indicators 

 

15s start time 

 

Three sensitivity settings via panel 

 

Compatible with TFA-0120 Universal Detector Base 

 

Technical Features

 

 

Power Input 

18V(min) 

 32V(max) 

Average Current Consumption 

80uA (@32V) 

Maximum Alarm Current 

3mA (@32V) 

Maximum External Device Current 

10mA (@32V) 

 (2K2 resistance limited) 

Alarm Threshold (approximate) 

H: 0.12, M: 0.15, L: 0.18 dB/m 

Operating Temperature Range 

-10

C ~ 55

C (14

F ~ 131

F) 

Humidity 

95% RH (max) 

Dimensions (mm) 

Ø110, h42

 

Housing Material 

White Color, ABS Plastic 

Used Cable Cut 

0.4mm ² ~ 1.5mm ²

 

Weight (incl. Base / excluding base) 

183 gr / 125 gr 

Start Time 

15 sn 

 

 

Indicator Leds

 

 

 

Blue Led 

Red Led 

Any error condition 

(dust or power failure) 

Blinks for 1s period 

In normal operating condition 

Blinks for 20s period 

In alarm condition 

It is constantly lit 

 

 

 

 

Terminals

 

 

Number 1 

Negative (-) supply input, Negative (-) supply output 

Number 2 

Negatif(-) input of the remote indicator 

Number 3 

Positive (+) input of remote indicator 

Number 4 

Positive (+) supply input, Positive (+) supply output 

Number 5 

Earth connection 

 

 
 

 

 
 

 
 

 
 

 

Warning: 

The product only works with TFP-121x, TFP-122x and TFP-123x Analogue Addressable 

Fire Alarm panels. 

Warning:

 Do not attempt to remove the electronic board from its plastic case. The electronic board is 

closed for your safety. Users should avoid from interference. 