Installation
Page 50
MDE-3985L Encore® Installation Manual · May 2006
For New and Existing Pumps and Dispensers with Fuel in Lines
(Purging through Nozzle)
1
Lift nozzle handle for hose being purged. (For Encore 300 purging, follow the procedure for
purging in the previous section for the selected meter.)
2
Place nozzle in approved container.
3
Slowly open nozzle until you obtain a slow, constant stream of fuel flow. (For SMART Meter
equipped units, never exceed the nozzle slow latch setting until fuel flow is steady.)
4
Purge system with the amount of fuel specified below:
5
Return nozzle to nozzle boot.
6
Empty approved container into appropriate product tank.
7
Repeat steps for each affected hose for each meter.
Installation Checklists
To ensure that proper and safe operation of all equipment and to maintain warranty coverage it
is required that MDE-4226 Encore/Eclipse Installation Checklist (Form A) be completed at
this time. The
Mechanical and Hydraulic Related Items
and
Electrical Related Items
checklists
on the following pages may be used as a guide. (Many of the items on the lists should already
have been checked by the electrician as covered earlier.)
Follow the checklists and perform all required inspections. Once the inspection has been
completed, insert MDE-4226, less your copy, in the dispenser electronic cabinet away from
and not touching any electronic components. Forms should be provided with each unit, if not,
contact the Gilbarco Veeder-Root Distributor. It is only necessary to complete the station
electrical inspection portions of the form (List 3) per form, per unit, at the station.
Note: Make copies of the checklists in this manual for actual use in order to preserve the
originals for future use. In this manner, you will always have an original to copy for use
in the future.
For
Pump This Amount
Start-ups (installing new systems)
35 gallons (130 liters) per hose
MDE-4226 Encore/Eclipse Installation Checklist (Form A) Name
In Following Checklists,
MDE-4226 Checklist
Refered To As
Individual Pump/Dispenser Hydraulic/Mechanical Related
List 1
Individual Pump/Dispenser Electrical Related
List 2
Station Electrical
List 3
Purging air at high flow rates through meter can permanently damage them. Noise is not
an indication of overspeed in many cases.
Overspeed meter damage is not covered by warranty. Follow all instructions carefully.
CAUTION