background image

18

Water Temperature Regulation 

WARNING

The higher the temperature setting, the greater the risk 
of scalding. Hot water can cause third degree burns in 
under one (1) second at 160

o

F (71

o

C), in five (5) sec-

onds at 140

o

F (60

o

C), and in thirty (30) seconds at 130

o

(54

o

C). In households where there are children, physically 

challenged individuals, or seniors, mixing valves for point 
of use are necessary as means of reducing the scalding 
potential of hot water.

When the water heater is plugged in for the first time, the 
gas control valve will start to heat the water to the factory 
adjusted temperature. To avoid any unintentional changes 
in the water temperature settings, the gas control valve has 
a tamper-resistant feature included for changing the tem-
perature setting. If you want to change this setting for either 
cooler or warmer water, the following steps are necessary:

1. “Wake up” the temperature indicators by holding down 

both the 

COOLER

 and 

HOTTER

 temperature adjust-

ment buttons at the same time for one (1) second (see 
Lighting Instructions). One or two of the temperature 
indicators will light up. These indicators will only remain 
on for thirty (30) seconds, if no further buttons are 
pressed. After thirty (30) seconds, the control will go 
back to “Sleep” mode, and both buttons will again have to 
be pressed to see the water temperature setting. Release 
both of the temperature adjustment buttons. 

See Figure 

12 

for an explanation of what each of the temperature indica-

tors mean.

 

To decrease the temperature

, press and release the 

COOLER button once. The temperature indicators will now 
display the new temperature setting. Press and release 
the 

COOLER

 button until you have reached the desired 

setting. 

HOLDING DOWN THE BUTTON WILL 

NOT CONTINUE TO LOWER THE SETTING

. The 

button must be pressed and released for each tempera-
ture change desired.

 

To increase the temperature

, press and release 

the HOTTER button once. The temperature indicators 
will now display the new temperature setting. Press and 
release the 

HOTTER

 button until you have reached the 

desired setting. 

HOLDING DOWN THE BUTTON 

WILL NOT CONTINUE TO RAISE THE SETTING

The button must be pressed and released for each tem-
perature change desired.

  To maximize the efficiency of this water heater and reduce 

the risk of scalding, it is recommended that the gas control 
valve be set at the setting below the large triangle (« »), 
which represents approximately 120°F (49°C).

2. When you have completed setting the control, wait thirty 

(30) seconds to see that the temperature indicators go 
off and the control enters “Sleep” mode. 

ALL OF THE 

TEMPERATURE INDICATORS WILL BE OFF 
DURING NORMAL OPERATION

. If at any time you 

see the indicators on, there may be a problem with the 
water heater and you should consult the Troubleshooting 
Guide of this document, or contact a trained service profes-
sional.

When hot water is drawn from the tank in frequent 
short bursts, a condition known as “stacking” is created. 
“Stacking” is the result of increased cycling of the burner and 
can produce very hot water temperatures at the hot water out-
let. Always remember to check the hot water coming out of 
any faucet with your hand before use. This will reduce the 
risk of scalding-related injuries. 

OPERATING INSTRUCTIONS

FLASHING

APPROXIMATE

TEMPERATURE

˚F (˚C)

70 (21) 

(Vacation)

110 (43)

115 (46)

120 (49)

125 (52) 

130 (54)

135 (57)

140 (60)

145 (63)

150 (66)

160 (71)

APPROXIMATE

TIME TO

CAUSE INJURY

N/A

5 Minutes

30 Seconds

5 Seconds

1.5 Seconds

Under 1 Second

DISPLAY

Figure 12

Summary of Contents for UG50 series

Page 1: ...quids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building From a neigh...

Page 2: ...er inspected immediately by a qualified service technician or the gas supplier WARNING Safety Information 3 Installation Instructions 4 Altitude 4 Location 4 Minimum Clearances 4 Venting 4 Venting Con...

Page 3: ...This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death c...

Page 4: ...vered by the panel Minimum Clearances The minimum clearances from combustible material for this water heater are Two 2 inches 5 1 cm from the sides and rear four 4 inches 10 2 cm from the front and ei...

Page 5: ...d States see Figure 4 This water heater must be vented directly to the outdoors either horizontally through the wall or vertically through the roof The venting must not be attached to an existing chim...

Page 6: ...2 X 3 is necessary for a three 3 inch 7 6 cm venting system This coupling must be installed as close as possible after the rubber transition fitting and in every case before the first elbow Vent Syste...

Page 7: ...orch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 12 inches 30 cm 9 inches 23 cm or 12 inches 30 cm C Clearance to outside corner D Clearance to ins...

Page 8: ...or wall same atmospheric pressure zone The air intake equivalent vent length must be equal to or less than the exhaust equivalent vent length and the air intake termination elbow shall be equipped wit...

Page 9: ...ke terminal must be at a minimum of eighteen 18 inches 45 7 cm from the exterior surface of the roof or anticipated snow accumulation level see Figure 2 The vertical terminations should be sealed with...

Page 10: ...ssemble parts while cement is fluid If you wait too long re coat pipe fitting 8 Push the vent pipe completely into the coupling turning as it goes until it bottoms out 9 Hold pipe and fitting together...

Page 11: ...ent system from IPEX be sure to install the two 2 inch 5 1 cm black restrictor screen from 0 to twenty five 25 feet 7 6 m If using the three 3 inch 7 6 cm concentric vent system from IPEX be sure to i...

Page 12: ...an result in property damage personal injury or death To protect from excessive pressure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requir...

Page 13: ...roved for natural and propane gases It is mandatory that a readily accessible manual shut off valve be installed in the gas supply line The gas supply manual shut off valve must be close to the water...

Page 14: ...1o F 105o C Installation Instructions for Water Heaters Approved for Combination Space Heating and Potable Water Heating see Figure 11 A water heater cannot be used for space heating only When using a...

Page 15: ...er is equipped with a check valve water meter or pressure reducing valve an expansion tank must be installed in the system This will prevent weeping from the water heater relief valve and premature fa...

Page 16: ...he appropriate primer and solvent based cement when necessary Has the venting been supported at the proper intervals Have precautions been taken against condensation flowing into the power venter Wate...

Page 17: ...ter immediately contact a qualified installer service agency or the gas sup plier WARNING DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed on t...

Page 18: ...he COOLER button until you have reached the desired setting HOLDING DOWN THE BUTTON WILL NOT CONTINUE TO LOWER THE SETTING The button must be pressed and released for each tempera ture change desired...

Page 19: ...switch to lock out mode and prevent the water heater from lighting After a flammable vapour incident has occurred and the flam mable vapours have dissipated the FV sensor is designed to automatically...

Page 20: ...common observation is hot water that smells like rotten eggs This phenomenon is the result of the reaction between the anode and hydrogen sulfide gas dissolved in the water which occurs frequently in...

Page 21: ...listed in the Troubleshooting Guide does not solve the problem or if your particular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Page 22: ...r Access Doors 7 Outer Access Door 8 Drain Valve 9 Overflow Tube 10 Dip tube 11 Magnesium Anode 12 Temperature Pressure Relief Valve 13 Baffle 14 Inlet Rubber Adaptor 15 Vacuum Switch Inlet 16 Vacuum...

Page 23: ...ion 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the power to the water heater for 10 seconds and then back on 2 If the above step did not clear the err...

Page 24: ...re Check with gas utility company Defective gas control valve Replace with new gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sedime...

Page 25: ...ter filled for first time Let water heater warm up Problem should go away If it per sists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater...

Page 26: ...in in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable wate...

Page 27: ...xed to the heater any non factory made or factory approved replace ment part s such as elements controls dip tubes relief valves etc 9 To any damage caused by not having the water heater installed adj...

Page 28: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Reviews: