background image

12

WARNING

When the installation is complete, visually inspect the 
venting system to make sure that all joints are properly 
connected and all instructions have been followed. Failure 
to properly install the venting system could result in 
property damage, personal injury, or death.

Condensation in the Venting System

In some installations, condensation will form in the horizontal 
runs of vent piping. In order to effectively control the con-
densate from adversely affecting the mechanical components 
of the water heater (draining back into the blower), a rubber 
adaptor with a drain outlet is mounted directly on the blower 
vent outlet. A plastic tube can be attached to this outlet to drain 
any condensate that has accumulated, away from the water 
heater. Make sure that the condensate removal tube flows to a 
suitable free-flowing drain.

Water Piping

Refer to 

Figure 8

 for a typical installation. Use of this lay-

out should provide a trouble-free installation for the life of 
the water heater. Before making the plumbing connections, 
locate the 

COLD

 water inlet and the 

HOT

 water outlet. 

These fittings are both 

3

/

4

” NPT male thread. Make sure 

that the dip-tube is installed in the cold water inlet. Install 
a shut-off valve close to the water heater in the cold water 
line. It is recommended that unions be installed in the cold 
and hot water lines so that the water heater can be easily 
disconnected, if servicing is required.

When assembling the hot and cold piping, use a good food 
grade of pipe joint compound, and ensure all fittings are tight. 

DO NOT APPLY HEAT TO THESE FITTINGS

 when 

making sweat connections to the water heater. Sweat tubing 
to threaded adaptors before connecting to the water heater. 

IT IS IMPERATIVE THAT NO HEAT BE APPLIED

 to 

the cold water inlet, as it contains a non-metallic dip-tube. 

This will result in premature failure of the fittings, 
which is not covered by the warranty

.

Temperature and Pressure-Relief Valve

WARNING

DO NOT

 plug the temperature and pressure-relief valve 

or its discharge line. 

DO NOT

 remove the relief valve. 

Make sure the relief valve is properly sized for the water 
heater. If the relief valve continuously discharges water, call a 
qualified service technician to correct the problem. Failure 
to follow these instructions can result in property damage, 
personal injury, or death.

To protect from excessive pressure and/or temperature, the 
manufacturer has installed a temperature and pressure-relief 
valve that meets the requirements of the Standard for Relief 
Valves and Automatic Gas Shut-Off Devices for Hot Water 
Supply Systems, CSA 4.4, in Canada, and ANSI Z21.22, in the 
United States. This relief valve has a maximum set pressure 
that does not exceed the hydrostatic working pressure of the 
water heater (150 psi = 1,035 kPa) and a BTU/h rating equal 
to or greater than the input rating, as shown on the water 
heater rating plate. It should never be plugged or removed 
from the opening marked for it on the water heater.

If this relief valve should need to be replaced, use only a new 
temperature and pressure-relief valve. Never install an old or 
existing relief valve, as it may be damaged or inadequate for 
the working requirements of the new water heater. This new 
relief valve must meet all local codes or, at a minimum, the 
requirements listed above. Never install any other type of valve 
between the relief valve and the water heater.

A discharge line must be installed into the relief valve. The 
discharge line:

•  Must not be smaller than the outlet pipe size of the relief 

valve. 

•  Must not terminate less than six (6) inches (15 cm) and 

not more than twelve (12) inches (30 cm) above floor.

•  Must not be restricted in any way. Do not thread, cap, or 

in any way restrict the end of this outlet.

• Must be of a material capable of withstanding 210

o

(99

o

C) without distortion.

•  Must be installed to allow complete drainage of the relief 

valve and discharge line.

•  Must terminate at an adequate free-flowing drain.

Pressure Build-up in a Water System 

When the water heater operates, the heated water 
expands creating a pressure build-up. This is a 
natural function and is one of the reasons for installing a 
temperature and pressure-relief valve. If the cold water sup-
ply line has a built-in water meter, check valve, or pressure-
reducing valve, a suitable expansion tank must be installed to 
prevent pressure build-up or water hammer effect. Otherwise, 
the warranty is void (

see Figure 8

). An indication of pressure 

build-up is frequent discharges of water from the relief valve. 
If the relief valve discharges water on a continuous basis, it 
may indicate a malfunction of the relief valve, and a qualified 
service technician must be called to have the system checked, 
and the problem corrected.

INSTALLATION INSTRUCTIONS

Summary of Contents for UG50 series

Page 1: ...quids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building From a neigh...

Page 2: ...er inspected immediately by a qualified service technician or the gas supplier WARNING Safety Information 3 Installation Instructions 4 Altitude 4 Location 4 Minimum Clearances 4 Venting 4 Venting Con...

Page 3: ...This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death c...

Page 4: ...vered by the panel Minimum Clearances The minimum clearances from combustible material for this water heater are Two 2 inches 5 1 cm from the sides and rear four 4 inches 10 2 cm from the front and ei...

Page 5: ...d States see Figure 4 This water heater must be vented directly to the outdoors either horizontally through the wall or vertically through the roof The venting must not be attached to an existing chim...

Page 6: ...2 X 3 is necessary for a three 3 inch 7 6 cm venting system This coupling must be installed as close as possible after the rubber transition fitting and in every case before the first elbow Vent Syste...

Page 7: ...orch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 12 inches 30 cm 9 inches 23 cm or 12 inches 30 cm C Clearance to outside corner D Clearance to ins...

Page 8: ...or wall same atmospheric pressure zone The air intake equivalent vent length must be equal to or less than the exhaust equivalent vent length and the air intake termination elbow shall be equipped wit...

Page 9: ...ke terminal must be at a minimum of eighteen 18 inches 45 7 cm from the exterior surface of the roof or anticipated snow accumulation level see Figure 2 The vertical terminations should be sealed with...

Page 10: ...ssemble parts while cement is fluid If you wait too long re coat pipe fitting 8 Push the vent pipe completely into the coupling turning as it goes until it bottoms out 9 Hold pipe and fitting together...

Page 11: ...ent system from IPEX be sure to install the two 2 inch 5 1 cm black restrictor screen from 0 to twenty five 25 feet 7 6 m If using the three 3 inch 7 6 cm concentric vent system from IPEX be sure to i...

Page 12: ...an result in property damage personal injury or death To protect from excessive pressure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requir...

Page 13: ...roved for natural and propane gases It is mandatory that a readily accessible manual shut off valve be installed in the gas supply line The gas supply manual shut off valve must be close to the water...

Page 14: ...1o F 105o C Installation Instructions for Water Heaters Approved for Combination Space Heating and Potable Water Heating see Figure 11 A water heater cannot be used for space heating only When using a...

Page 15: ...er is equipped with a check valve water meter or pressure reducing valve an expansion tank must be installed in the system This will prevent weeping from the water heater relief valve and premature fa...

Page 16: ...he appropriate primer and solvent based cement when necessary Has the venting been supported at the proper intervals Have precautions been taken against condensation flowing into the power venter Wate...

Page 17: ...ter immediately contact a qualified installer service agency or the gas sup plier WARNING DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed on t...

Page 18: ...he COOLER button until you have reached the desired setting HOLDING DOWN THE BUTTON WILL NOT CONTINUE TO LOWER THE SETTING The button must be pressed and released for each tempera ture change desired...

Page 19: ...switch to lock out mode and prevent the water heater from lighting After a flammable vapour incident has occurred and the flam mable vapours have dissipated the FV sensor is designed to automatically...

Page 20: ...common observation is hot water that smells like rotten eggs This phenomenon is the result of the reaction between the anode and hydrogen sulfide gas dissolved in the water which occurs frequently in...

Page 21: ...listed in the Troubleshooting Guide does not solve the problem or if your particular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Page 22: ...r Access Doors 7 Outer Access Door 8 Drain Valve 9 Overflow Tube 10 Dip tube 11 Magnesium Anode 12 Temperature Pressure Relief Valve 13 Baffle 14 Inlet Rubber Adaptor 15 Vacuum Switch Inlet 16 Vacuum...

Page 23: ...ion 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the power to the water heater for 10 seconds and then back on 2 If the above step did not clear the err...

Page 24: ...re Check with gas utility company Defective gas control valve Replace with new gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sedime...

Page 25: ...ter filled for first time Let water heater warm up Problem should go away If it per sists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater...

Page 26: ...in in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable wate...

Page 27: ...xed to the heater any non factory made or factory approved replace ment part s such as elements controls dip tubes relief valves etc 9 To any damage caused by not having the water heater installed adj...

Page 28: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Reviews: