from degradation by flue gases from the vent
termination.
Co-axial Flexible Vent Pipe Kit (Vent Kit)
DO NOT
install this water heater if any of the parts
are damaged. The vent kit must be properly
installed. All horizontal runs of piping must have a
minimum rise of 1/4 inch per foot (21 mm/m) of run.
It is important to completely seal all the vent kit joints
where indicated in these instructions with high
temperature silicone sealant. A tube is supplied with
every direct vent water heater. Failure to properly
install the vent kit can result in property damage,
personal injury, or death.
This water heater has been shipped with a complete
vent kit. This kit includes:
• A three (3) inch (7.6 cm) inner, five (5) inch (12.7 cm)
outer co-axial “Wind-Tamer” vent termination.
• An outer wall mounting plate
• An inner wall back plate
• A length of three (3) inch (7.6 cm) inner, six (6) inch
(15.2 cm) outer co-axial flexible vent pipe with
reducer installed
• A six (6) inch (15.2 cm) to five (5) inch (12.7 cm)
reducer
• Two (2), three (3) inch (7.6 cm) hose clamps
• A six (6) inch (15.2 cm) hose clamp
• A tube of high temperature silicone
• Eight (8) wall anchors
• Eight (8) #10 x 1" screws
• Four (4) washers
• Six (6) 1/2" thread cutting screws
Vent Kit Installation
The following instructions detail the installation of the
co-axial flexible vent pipe kit supplied with every water
heater.
1) Place the water heater in it's final position (refer to
the
Location and Minimum Clearances
sections
for correct positioning requirements) and verify if
you are able to install the vent kit in accordance with
the specifications illustrated in
Figure 3
.
Note:
a) The vent kit of this water heater can be installed
in any 360˚ configuration as long as the proper
clearances for installation, plumbing, operation,
and servicing are maintained (
see Figure 3a
).
b) The minimum inner radius for the vent pipe
curvature is 11" (27,9 cm) (use the water heater
outside radius as reference,
see Figure 3b
).
c) The maximum vent pipe curvature is 90˚
(
see Figure 3c
).
d) You can’t use both setup #3 and setup #4 on the
same vent pipe installation.
2) Locate where the vent termination is going to be
installed and cut a five and one half (5 1/2) inch
(14 cm) diameter clearance hole through the wall
(
see Figure 4
).
3) Outside of the building, position the outer wall
mounting plate and the termination kit over the
center of the wall opening. Mark the hole locations
for the mounting screws. Drill 1/4'' diameter holes in
the wall for the four (4) wall anchors. Install the wall
anchors and attach the outer wall mounting plate
5
Grade Line
S
2'' min.
2'' min.
18'' min.
18'' min.
1'' min. around
0'' min.
12'' min.
18'' min.
4'' min.
4'' min.
4'' min.
2'' min.
Figure 1
WARNING
A
INSTALLATION INSTRUCTIONS