Programming
Switch G1:
When this switch is open, the photoelectric cell is enabled only
during closing.
When this switch is closed, the photoelectric cell is enabled during
opening and closing.
Switch G2:
When this switch is closed, the automatic closing function is
enabled.
When this switch is open, the automatic closing function is
disabled.
Switch G3:
When this switch is closed, the opening-only command is enabled
- see input terminal 13. The closing command may be given
when the gate is open and not moving, with the button or in
automatic.
When this switch is open, the sequential open-pause-close-open
command is enabled.
Adjustment
T1 TRIMMER
regulates the operating time of the motors from a
minimum of 2 seconds to a maximum of aproximately 105
seconds.
T2 TRIMMER
regulates the automatic closing pause time from a
minimum of 2 seconds to a maximum of about 150 seconds.
T3 TRIMMER
regulates the delay time of the swing which contacts
the rabbet in the closing phase (motor 1), maximum 20 seconds.
Protection
F1
- T160 mA Low-voltage input protection.
F2
- F5 A 220-230 V, 50-60 Hz protection for loads connected
to the mains.
Photoelectric cell
When the photoelectric cell is programmed for closing (switch
G1 is open), if it is intercepted during closing, it interrupts the
gate and reverse its motion from closing to opening when it is
Single-phase motor 1. The motor capacitor is connected
to terminals 1-3.
Single-phase motor 2. The motor capacitor is connected
to terminals 4-6.
220-230 V, 50-60 Hz flashing light.
220-230 V, 50-60 Hz power supply.
Protective ground terminal for connecting yhe main
ground wire.
Functional ground terminal for grounding the control unit’s
metal parts.
Sequential open-stop-close-open button, or opening only.
Normally open contact.
Stop or emergency button. Normally closed contact.
Photoelectric cell. Normally closed contact.
Input common: buttons, photoelectric cell.
24 VAC outputs for powering the photoelectric cell, radio
receiver in container, etc..
12 VDC electric lock.
12 VDC 3 W indicator light.
Antena coaxial cable connection.
DEVICES FOR PROGRAMMING, ADJUSTMENT, AND PROTECTION
freed.
When the photoelectric cell is programmed for closing and
opening (switch G1 closed), if it is intercepted during the closing,
it stops the gate. When the photoelectric cell is freed the gate
will reopen.
If the photoelectric cell is intercepted during the opening phase,
it stops the gate. When the photoelectric cell is freed the gate
will continue to open.
Safety pneumatic frame for anti-entrainment protection
The N.C. contacts of the anti-entrainment pneumatic frame must
be connected in series to the N.C. contact of the stop button on
terminal 14. If the anti-entrainment, anti-crushing pneumatic
frame is intercepted, the opening or closing motion of the gate
stops.
FUNCTION CONTROL LEDS
L1
- Green LED - Opening command.
L2
- Red LED - Stop button.
L3
- Red LED - Photocell.
INDICATOR LIGHT
The indicator light turns on when the gate begins opening.
It remains lit when the gate has stopped and turns off when the
gate begins closing.
ELECTRIC LOCK
The control of a single electric lock has been provided, which is
enabled for approximately 3 seconds when the opening function
starts.
FLASHING LIGHT
The 220-230 V 50-60 Hz flashing light starts functioning
simultaneously with the start of the motor.
CONNECTOR C1
Radio receiver card: if the 10 dip switches for code programming
are present, set the same sequence as set on the transmitter. If
the 10 dip switches are absent the radio receiver is self-learning
and thus the instructions at the end of this handbook must be
followed.
TECHNICAL OPERATING CHARACTERISTICS
- Temperature range: -20 à +70
°
C.
- Humidity: < 95 % without condensation.
- Voltage: 220-230 V + 10 %.
- Fréquency: 50-60 Hz.
- Max. card absorption (excluding external charges): 100 mA.
- Micro power cutoff (at max load and min voltage): 20mS.
- Max. power on motor output: 1 CV (736 W).
- Max. load on warning light output: 12 VCC 3 W.
- Max. load on flashing light: 40 W 250 V cosø= 1.
- Available courrent on photocell output: 0,2 A 24 VAC.
- Max. load on electrolock output: 12 VCC 12VA max.
- Radio eceiver connector with supply: 12 V + 15%.
- Degree of box protection: IP 55.
- All inputs must be used as clean contacts, as supply is
generated inside the card and arranged to guarantee double or
reinforced insulation with respect to the live parts.
- All inputs, both functional and safety, are controlled by a
programmable integrated circuit (PAL).
- The stop input (terminal 14 - N.O. contact), other than resetting
the programmable integrated circuit, does not supply the tripping
coil if it remains open; it can therefore, be used to unconditionally
stop the motor in situation of risk to the operator.