E31.0.12.6C-06
Mounting and operating manual GIA 20 EB with electrically insulated supply
page 28 of 32
Note: Depending on the inertia of your cooling circuit an overshooting of the temperature may be possible.
Example: You want to have an alarm monitoring for the cooling chamber mentioned above. The
alarms should start when the temperature will be rising above
–15°C or falling
below
–30°C. Therefore you have to select –15°C for the maximum alarm-value “Al.Hi“
and
–30°C for the minimum alarm-value “AL.Lo“.
The alarm will be starting after the temperature rises above
–15°C and stays above –
15°C for the entered delay time or after it had been falling below
–30°C and stays below
–30°C for the entered delay time.
Please note that the alarm-outputs are inverted! This means, that the output will be active when
there is no alarm.
9.4. Minimum/maximum-alarm (individual or common)
This chapter describes how to configure the device‘s alarm boundaries for min-/max-alarm-
monitoring. Thi
s instruction demands that you selected “
AL.F1
“ or “
AL.F2
“ as your desired output
function like it is explained in chapter 7.1.
The alarm-outputs are inverted.
That the output will be active when there is no alarm
The display has to show
AL. K,
.
Parameter
Button 1
Wert
Button 2 / 3
Description
AL. K,
AL.L O
... Max. display range
Maximum alarm-value
AL.L O
Min. display range ...
AL. K,
Minimum alarm-value
A.DEL
0 ... 9999
Alarm delay. Time [in sec] before the alarm
gets active.
Finish Adjustment:
Press
Button 1
as often till the device executes a reset. The values will be stored at it.
Example: You want to have a temperature alarm-monitoring of a greenhouse. The alarm should
start when the temperature rises above 50°C or falls below 15°C.
Therefore your settings will be 50°C for the maximum alarm-
value “AL.HI“ and 15°C for
the minimum alarm-
value “AL.Lo“. The alarm will be starting after the temperature rises
above 50°C and stays above 50°C for the entered delay time or after it had been falling
below 15°C and stays below 15°C for the entered delay time..
10. Min-/max-value storage
The device features a minimum/maximum-value storage. In this storage the highest and lowest
measured value are saved.
Button
Description
Min.-Value Press short
The device will display “Lo“ briefly, after that the
min-value is displayed for about 2 sec.
Max.-Value Press short
The device will display “Hi“ briefly, after that the
max-value is displayed for about 2 sec.
Erase
Press together
>2 seconds
the device will display “CLr“ briefly, after that the
min/max-values are set to the
current displayed value.