Mounting and operating manual GIA 20 EB with electrically insulated supply
page 27 of 32
9.2. 2-point-controller, 3-point-controller
This chapter describes how to configure the device as a 2-point-controller or 3-point-controller.
This
instruction demands that you selected “
2P
“ or “
3P
“ as your desired output function like it is ex-
plained in chapter 7.1.
The display has to show
1.ON
.
Parameter
Button 1
Value
Button 2 / 3
Description
1.ON
Min. display range ... Max. display range
Turn-on-point of output 1
1.OFF
Min. display range ... Max. display range
Turn-off-point of output 1
2.ON
only with
3P
Min. display range ... Max. display range
Turn-on-point of output 2
2.OFF
only with
3P
Min. display range ... Max. display range
Turn-off-point of output 2
Finish adjustment:
Press
Button 1
as often till the device executes a reset. The values will be stored at it
Example: You want to control the temperature of a heating coil, with a hysteresis of +2°C, to
120°C. Therefore you will have to select the turn-on-
point “1.on“ to 120°C and the
turn-off-
point to “122°C“. When your heating coil temperature falls below 120°C it will be
turned on. When the temperature rises above 122°C the heating coil will be turned off.
Note: Depending on the inertia of your heating coil an overshooting of the temperature
may be possible
9.3. 2-point-controller with alarm function
This chapter describes how to configure the device as a 2-point-controller with alarm function.
This instruction demands that you selected “
2P.AL
as your desired output function like it is ex-
plained in chapter 7.1.
The display has to show
1.ON
.
Parameter
Button 1
Value
Button 2 / 3
Description
1.ON
Min. display range ... Max. display range
Turn-on-point of output 1
1.OFF
Min. display range ... Max. display range
Turn-off-point of output 1
AL. K,
AL.L O
... Max. display range
Maximum alarm-value
AL.L O
Min. display range ...
AL. K,
Minimum alarm-value
A.DEL
0 ... 9999
Alarm delay. Time [in sec] before the
alarm gets active.
Finish Adjustment:
Press
Button 1
as often till the device executes a reset. The values will be stored at it.
Alarm-outputs are inverted! This means, that the output will be active when
there is no alarm!
Example: You want to control the temperature of a cooling chamber between
–20°C and –22°C.
Therefore you will have to select
–20°C for the turn-on-point 1 “1.on“ and –22°C for the
turn-off-
point 1 “1.off“. When the temperature rises above –20°C the device turns its out-
put 1 on, when falling below
–22°C the device will turn its output 1 off .