DGF7 Display

 

reference

 

manual, rev. 1, feb 22, 2022 

Ground

 

Fault

 

Systems

 

B.V. 

2.

 

F

UNCTIONALITY

 

 

2.1

 

Pushbuttons 

 
The DGF7 Display has two pushbuttons, marked ‘SHOW TRIP’ and ‘RESET’. 
With these two buttons a variety of reading and setting options can be performed. 
 

2.1.1

 

G/F current display 

 
When left untouched (except while in parameter set-up mode, see 

section 3

), the DGF7 Display will 

always return to showing the current flowing to ground, commonly referred to as ‘G/F current’. The user 
has two options for showing this current: 

 

Relative format: as a percentage of the G/F Trip Level. The G/F Trip Level is set by means of 
dipswitches 1, 2 and 3 on the DGF7-3 base unit. It is the intention that the user checks the ‘%’ box 
on the DGF7 Display’s front panel with a marker. 

 

Absolute format, i.e. in engineering units: A or kA. In this mode the DGF7 Display uses the P4 
parameter (see 

section 3

), specifying the CS configuration, to calculate absolute from relative 

current. It is the intention that the user checks the ‘A’ or ‘kA’ box on the DGF7 Display’s front panel 
with a marker, as is appropriate for the selected configuration. Absolute format is the factory default 

setting. 

Normally the system shows the G/F current’s actual value, refreshing it every 0,5 seconds. When the 

DGF7-3 base unit is in a tripped state, with the fault current removed, the value flashes and refers to the 
situation just prior to trip. If the fault current is still active, the actual value will be displayed. 
 
When the G/F current exceeds the system’s measuring range, the display shows  

Out 

  , meaning ‘Out of 

range’. Depending on various internal variables, the maximum value that can be represented (whether in 
relative or absolute format) before resorting to the ‘Out of range’ indication varies from around 400 to 

800 % of the G/F Trip Level. 

Back to Table 2.

 

 

2.1.2

 

G/F Trip Level display 

 
The DGF7 Display is able to show the G/F Trip Level Setting (by holding the ‘SHOW TRIP’ button longer 
than 2 seconds). All supported configurations are shown in 

table 1

For the configurations the user needs 

to set internal parameter P4 as is detailed in 

section 3

.  

 

2.1.3

 

Trip code display 

 

Pushing the ‘SHOW TRIP’ button when the G/F current is shown, calls forward the trip code display. If no 
trip condition is present, the display shows as  

tr:--

 . Further operator action lacking, the display will 

return to G/F current after 2 seconds. If, on the other hand, a trip condition is present, the format 
becomes  

tr:xx

  in which 

xx

 is the trip code, indicating the cause of the trip. The 

xx

 codes are explained 

on the front panel of the DGF7 Display. A complete list with more extensive explanations is available in 

section 7.3

. Further operator action lacking, the display will return to G/F current after 10 seconds. 

Pushing the ‘SHOW TRIP’ button again while the 

tr:xx

 trip code is on the display makes the display return 

to G/F current instantaneously. 
Pressing the ‘RESET’ button while the 

tr:xx

  trip code is on the display, is interpreted as a request to 

reset the trip. Both the trip relay and the trip registration will be reset IF possible. During reset action the 
display will show a moving dot, then show the 

tr:--

  format of the trip code and return to G/F current  

Summary of Contents for DGF7

Page 1: ...DGF7 Display reference manual Ground Fault Systems B V Rigtersbleek Aalten 4B15 7521 RB Enschede The Netherlands www groundfaultsystems com info groundfaultsystems com Tel 31 53 4318628 CofC 55400914...

Page 2: ...2 Datalink error code 6 3 PARAMETER SETTING 7 3 1 Display Settings 7 3 2 Display setup procedure 7 4 CONNECTIONS AND PRECAUTIONS 8 5 TECHNICAL SPECIFICATIONS 9 5 1 Serial datalink circuit 9 5 2 Termi...

Page 3: ...arameters inside the display itself that modify its behaviour The DGF7 Display has settable parameters to enable the user to tailor the DGF7 Display to their needs Relay Test on off G F Current Displa...

Page 4: ...xceeds the system s measuring range the display shows Out meaning Out of range Depending on various internal variables the maximum value that can be represented whether in relative or absolute format...

Page 5: ...ful when pulse tripping a breaker that also supplies control voltage to the G F protection system Especially when several systems control one single breaker with their relay contacts in parallel which...

Page 6: ...is already tripped the display will show a 1 5 seconds message See chapter 3 for the parameter settings 2 1 7 LCD test The LCD panel can be tested at all times by keeping the RESET button pressed long...

Page 7: ...p Level that is set on the DGF7 3 dipswitches please check the box on the front panel 1 1 Absolute mode G F Current is displayed in A or kA as is applicable If a 5000 5 interposing CT is used check th...

Page 8: ...rt terminals Terminals will accept 0 5 2 5 mm2 20 14 AWG solid or stranded conductors The user may want to identify the following terminals as indicated on the display s product label S1 for connectin...

Page 9: ...ollution degree 3 over voltage category III Insulation stripping length 7 mm Torque 0 4 0 6 Nm Field wiring 0 5 2 5 mm2 VDE 20 14 AWG UL CSA Cu solid or stranded 5 3 Environment Operating temperature...

Page 10: ...4 3 Radiated electromagnetic field immunity EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN...

Page 11: ...L R R R L R R R 0 030 A 0 100 A 0 250 A 0 37 A 0 50 A 1 00 A 3 00 A 0 060 A 4 5 6 Ground Fault Trip Delay time and Trip Inhibit L L L L L R L R L L R R R L L R L R R R L R R R 20 ms without Trip Inhi...

Page 12: ...A 0 37 A 0 37 kA 0 74 A 1 48 A 7 4 A 37 A 0 50 A 0 50 A 0 50 kA 1 00 A 2 00 A 10 0 A 50 A 1 00 A 1 00 A 1 00 kA 2 00 A 4 0 A 20 0 A 100 A 3 00 A 3 00 A 3 00 kA 6 0 A 12 0 A 60 A 300 A 0 060 A 0 060 A...

Page 13: ...ream device failed to trip The DGF7 3 then tripped as a last resort The contactor should be inspected since its contacts may well be damaged 04 EXTERNAL CS OPEN CIRCUIT The connection to an external C...

Page 14: ...PAGE 14 OF 15 DGF7 Display reference manual rev 1 feb 22 2022 Ground Fault Systems B V 7 4 Figure 1 Typical Field Connection using DGF7 3 with built in core balance remote reset and DGF7 Display...

Page 15: ...PAGE 15 OF 15 DGF7 Display reference manual rev 1 feb 22 2022 Ground Fault Systems B V 7 5 Figure 2 Dimensions DGF7 Display...

Reviews: