DGF7 Display
reference
manual, rev. 1, feb 22, 2022
Ground
Fault
Systems
B.V.
7.2
Table 2 - DGF7 Display settings versus current read-out
Values are primary currents.
No.
0 (a)
0 (b)
1
2
3
4
DGF7-3
setting
Internal/
external
500:1
Interposing
5000:5
External
1000:1
External
2000:1
External
10.000:1
Interposing
500:5
0,030 A 0,030 A 0,030 kA 0,060 A 0,120 A 0,60 A
3,00 A
0,100 A 0,100 A 0,100 kA 0,200 A 0,40 A 2,00 A 10,0 A
0,250 A 0,250 A 0,250 kA 0,50 A 1,00 A 5,0 A 25,0 A
0,37 A 0,37
A 0,37 kA 0,74 A 1,48 A 7,4 A 37
A
0,50 A 0,50
A 0,50 kA 1,00 A 2,00 A 10,0 A 50
A
1,00 A 1,00
A 1,00 kA 2,00 A 4,0 A 20,0 A 100
A
3,00 A 3,00
A 3,00 kA 6,0 A 12,0 A 60
A 300
A
0,060 A 0,060 A 0,060 kA 12,0 A 24,0 A 120
A 600
A
Note: When using a 5000:5 interposing CT, the user needs to remember that displayed currents
), the ‘kA’ box can be checked with a marker on the display’s front panel,
making this obvious.
The G/F Trip Level can be called forward by keeping the ‘SHOW TRIP’ pushbutton pressed longer
than 2 seconds. The information remains visible until the pushbutton is released.
Back to G/F Trip Level display.