DGF7 Display
reference
manual, rev. 1, feb 22, 2022
Ground
Fault
Systems
B.V.
7.
T
ABLES
AND
FIGURES
7.1
Table
1 - DGF7-3 dipswitch settings
‘R’ denotes right and ‘L’ denotes left.
Values are primary currents for a 500:1 ratio internal or external Current Sensor.
For other ratio’s see
Switch
no.
Parameter
Set
to
Meaning
1 2 3
Ground Fault
Trip level
L L L ♦
L L R
L R L
L R R
R L L
R L R
R R L
R R R
0,030 A
0,100 A
0,250 A
0,37 A
0,50 A
1,00 A
3,00 A
0,060 A
4 5 6
Ground Fault
Trip Delay time
and Trip Inhibit
L L L ♦
L L R
L R L
L R R
R L L
R L R
R R L
R R R
20 ms
without Trip Inhibit
20 ms
with Trip Inhibit
100 ms
without Trip Inhibit
100 ms
with Trip Inhibit
300 ms
without Trip Inhibit
300 ms
with Trip Inhibit
1 s
without Trip Inhibit
3 s
without Trip Inhibit
7 8
Operating Mode
L L ♦
L R
R L
R R
Continuous Non-Failsafe operation
Continuous Failsafe operation
Pulsed Non-Failsafe operation
Pulsed Failsafe operation
♦ Factory settings
Back to G/F Trip Level display.