GFS DGF7 Reference Manual Download Page 5

 

P

AGE

 

5

 

OF

 

15

 

DGF7 Display

 

reference

 

manual, rev. 1, feb 22, 2022 

Ground

 

Fault

 

Systems

 

B.V. 

2 seconds later. Note however, that if at the time of reset a different trip was already lurking, the old trip 

registration will clear giving way to the new one, and the trip relay will remain activated without glitches. 
Resetting a trip will be refused if the cause of the trip has not cleared yet. In that case the display will 
show a 1,5 seconds message ‘---‘, then return to the trip code. Of course one should first clear the fault 

in the field that caused the current increase in the first place before resetting, or else the DGF7-3 will 
reset its relay and trip out immediately again. 
Resetting of the trip relay is meaningless if dipswitches 7 and 8 on the DGF7-3 base unit are set for 
Pulsed Relay Operating Mode. However, the registration of the trip behaves as described above in 

conjunction with the ‘RESET’ pushbutton. 
 

2.1.4

 

Trip code display during power down situations 

 

When the DGF7-3 base unit loses control voltage, it sends out trip status information on its datalink 

before shutting down. The DGF7 Display receives this information, stores it in memory and then shuts 
down itself, which shows by the LCD panel blanking. 
Thanks to a built-in backup power source the trip information can be retrieved for at least ten hours after 

loss of control voltage. Pressing the ‘SHOW TRIP’ button will bring forward the trip code display as it was 
described above, revealing whether or not the system was tripped at the loss of control voltage, and if 

so, what was the cause of the trip-out. The information remains visible until the pushbutton is released or 
backup power is exhausted.  
This feature is useful when pulse tripping a breaker that also supplies control voltage to the G/F 

protection system. Especially when several systems control one single breaker (with their relay contacts 
in parallel), which prevents the user from having to figure out which of them caused a given trip without 

having live systems anymore. 
For as long as control voltage remains absent, no other functionality than the one described here is 
available. 
The memorised trip information will reset automatically when control voltage is restored. If the DGF7-3 is 
still in a tripped state, the Display will first show 

tr:xx

 , than 

 ---

  and finally 

0,000

  or the actual G/F 

current value. The previous trip value is lost. 

 

2.1.5

 

Reset function 

 

The DGF7 Display can be used to reset the DGF7-3 after a trip occurred. A reset will only be granted if 
the cause of the trip is not present anymore.  
To reset the DGF7-3: 

 

Press the ‘SHOW TRIP’ button to read the trip cause. 

 

Press the ‘RESET’ button to reset the indicated trip, the LCD shows a moving dot, followed by 

tr:--

 , 

then goes back to normal current read-out. 

If the cause of the trip is cleared but another one is lurking, then pressing the ‘RESET’ button will reset 
the trip indication on the LCD and the new trip code is shown. The relay of the DGF7-3 however will 
remain in the trip state, without glitches. 
 

2.1.6

 

Relay test 

 

Keeping the ‘SHOW TRIP’ button pressed and then pressing the ‘RESET’ button invokes a test, which 
switches an AC voltage onto the CS sensor input of the DGF7-3 base unit’s built-in processor. The voltage 

is scaled to simulate a residual current of 1,5 – 3 times the G/F Trip Level setpoint. The base unit will trip 
on G/F after the delay defined on its dipswitches (plus 0,4 s). 
The trip code 

tr:00

  is called forward by pressing the ‘SHOW TRIP’ button. The ‘RESET’ button can then 

be pushed to reset the trip. You cannot reset without first pressing the ‘SHOW TRIP’ button. 

Summary of Contents for DGF7

Page 1: ...DGF7 Display reference manual Ground Fault Systems B V Rigtersbleek Aalten 4B15 7521 RB Enschede The Netherlands www groundfaultsystems com info groundfaultsystems com Tel 31 53 4318628 CofC 55400914...

Page 2: ...2 Datalink error code 6 3 PARAMETER SETTING 7 3 1 Display Settings 7 3 2 Display setup procedure 7 4 CONNECTIONS AND PRECAUTIONS 8 5 TECHNICAL SPECIFICATIONS 9 5 1 Serial datalink circuit 9 5 2 Termi...

Page 3: ...arameters inside the display itself that modify its behaviour The DGF7 Display has settable parameters to enable the user to tailor the DGF7 Display to their needs Relay Test on off G F Current Displa...

Page 4: ...xceeds the system s measuring range the display shows Out meaning Out of range Depending on various internal variables the maximum value that can be represented whether in relative or absolute format...

Page 5: ...ful when pulse tripping a breaker that also supplies control voltage to the G F protection system Especially when several systems control one single breaker with their relay contacts in parallel which...

Page 6: ...is already tripped the display will show a 1 5 seconds message See chapter 3 for the parameter settings 2 1 7 LCD test The LCD panel can be tested at all times by keeping the RESET button pressed long...

Page 7: ...p Level that is set on the DGF7 3 dipswitches please check the box on the front panel 1 1 Absolute mode G F Current is displayed in A or kA as is applicable If a 5000 5 interposing CT is used check th...

Page 8: ...rt terminals Terminals will accept 0 5 2 5 mm2 20 14 AWG solid or stranded conductors The user may want to identify the following terminals as indicated on the display s product label S1 for connectin...

Page 9: ...ollution degree 3 over voltage category III Insulation stripping length 7 mm Torque 0 4 0 6 Nm Field wiring 0 5 2 5 mm2 VDE 20 14 AWG UL CSA Cu solid or stranded 5 3 Environment Operating temperature...

Page 10: ...4 3 Radiated electromagnetic field immunity EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN...

Page 11: ...L R R R L R R R 0 030 A 0 100 A 0 250 A 0 37 A 0 50 A 1 00 A 3 00 A 0 060 A 4 5 6 Ground Fault Trip Delay time and Trip Inhibit L L L L L R L R L L R R R L L R L R R R L R R R 20 ms without Trip Inhi...

Page 12: ...A 0 37 A 0 37 kA 0 74 A 1 48 A 7 4 A 37 A 0 50 A 0 50 A 0 50 kA 1 00 A 2 00 A 10 0 A 50 A 1 00 A 1 00 A 1 00 kA 2 00 A 4 0 A 20 0 A 100 A 3 00 A 3 00 A 3 00 kA 6 0 A 12 0 A 60 A 300 A 0 060 A 0 060 A...

Page 13: ...ream device failed to trip The DGF7 3 then tripped as a last resort The contactor should be inspected since its contacts may well be damaged 04 EXTERNAL CS OPEN CIRCUIT The connection to an external C...

Page 14: ...PAGE 14 OF 15 DGF7 Display reference manual rev 1 feb 22 2022 Ground Fault Systems B V 7 4 Figure 1 Typical Field Connection using DGF7 3 with built in core balance remote reset and DGF7 Display...

Page 15: ...PAGE 15 OF 15 DGF7 Display reference manual rev 1 feb 22 2022 Ground Fault Systems B V 7 5 Figure 2 Dimensions DGF7 Display...

Reviews: