CAL Menu
(frequency)
• K-factor
• K-factor decimal
• Upper display timebase
• Totalizer reset
• Totalizer multiplier
• Display averaging
• Display decimal
• Contrast adjust
• Security code
(Analog)
• Range selection
• Minimum flow rate
• Maximum flow rate
• Totalizer reset
• Totalizer multiplier
• Display averaging
• Display decimal
• Contrast adjust
setpoint, hysteresis etc.
The OUTPUT menu provides access to the functions
which define and control all analog output signals,
i.e. 4 to 20 mA, 0 to 5 VDC etc.
CAL
OUTPUT Menu
• Minimum flow rate
• Maximum flow rate
• Low output adjust
• High output adjust
OUTPUT
RELAY Menu
(LO/HI)
• Relay 1 LO/HI
• Relay 1 setpoint
• Relay 1 hysteresis
• Relay 2 LO/HI
• Relay 2 setpoint
• Relay 2 hysteresis
(Pulse)
• Relay 1 Pulse
• Relay 1 pulse flow
unit setting
• Relay 2 Pulse
• Relay 2 pulse flow
unit setting
RELAY
Note:
A security function is
provided which allows the user
to "lock out" the calibration
menus, restricting access to
calibration settings. See Figure
14 .
All menus are loop type menus
which repeat until
FLOW
is
pressed.
All menus operate using a standard sequence:
1. Press:
MOD
to enable calibration sequence.
2. Enter security code (when active) using:
FLOW
; press:
ENTER
3. Select menu:
CAL
RELAY
OUTPUT
; press menu key to select item.
4. Press:
MOD
to enable modifying item.
5. Alter item using:
FLOW
; press:
ENTER
to save entry.
6. Press corresponding menu key to advance to next menu item.
7. Repeat steps 4-6 for each menu item. Exit menu by pressing:
FLOW
11