SECULOGIC TZ320
8
Commissioning
Commissioning
4
Preconditions
4.1
Doors with electrical locks along escape routes must be taken into operation after the manufacturer has certified
their suitability for the intended purpose. In addition, the correct installation and correct function of the electri-
cal lock must be verified by a specialist.
Service mode
4.2
To configure the door control unit, Service mode must be selected.
Activate service mode
4.2.1
Preconditions: No alarm is active.
The burglary alert system is switched off.
Turn the key to the left and hold it for about ten seconds.
X
The right LED lights up green, and the left and lower LEDs are off.
à
Disabling service mode
4.2.2
Do not take any action for three minutes or, in the Service menu, select “End service mode”.
X
The door control unit is then in its normal state again.
à
Connecting service terminal ST220 with door control unit
4.2.3
The service terminal is connected with the door control unit through an infrared interface.
Service terminal ST220
1
Infrared interface to TZ320
2
Hold the service terminal in front of the control unit and press the On key for about one second.
X
The service terminal is switched on.
à
Press the Esc key.
X
The top menu of the service menu appears.
à
Settings
4.3
Settings can be changed only with service terminal ST220.
Changing times, such as date, temporary unlocking time, pre-alarm time and alarm time.
à
Setting bus functions, such as air-lock function, BMA, EMA or ZSU.
à
Assigning functions to the inputs and outputs.
à
Assigning a bus address to log on to the bus system.
à
Activating the built-in timer.
à