Installation and assembly
Installation and assembly
3
WARNING!
Risk of death through electric shock.
Installation must be performed only by GEZE-approved specialist personnel.
X
Check that all cables are voltage-free before installation.
X
Preconditions
3.1
Cables are routed according to GEZE cabling diagram
à
Miniature circuit-breakers as primary, mains-side disconnectors
à
Observation of standards VDE 0100 und VDE 0815 for laying cables
à
Tamper-proof cable routing according to VDE 0833 (surface-mounted cables in steel conduit)
à
For flush-mounted cabling, flush-mounted sockets (depth 62.5 mm) at a mounting height of 850 mm from
à
upper edge of floor and up to 1200 mm for the emergency button
Installing the flush-mounted door control unit
3.2
These instructions describe the recommended installation of the a flush-mounted door control unit using the
TZ320BSN as an example.
Lay mains cable and ribbon cable in the flush-mounted sockets.
X
Connect cable to terminal blocks according to terminal diagram.
X
Connect and fit the PSU.
X
Connect the door control module with the key switch and the key switch with the emergency exit sign using
X
the ribbon cable.