GEZE SecuLogic TZ320 Installation And Commissioning Instructions With Terminal Diagram Brief Instructions Download Page 1

1

GEZE 

SECULOGIC 

TZ320 

Emergency Exit System

Door Control Unit

GB   Installation and Commissioning 

    Instructions with Terminal Diagram
    Brief instructions

Summary of Contents for SecuLogic TZ320

Page 1: ...1 GEZE SECULOGIC TZ320 Emergency Exit System Door Control Unit GB Installation and Commissioning Instructions with Terminal Diagram Brief instructions...

Page 2: ...6 4 Unlocking through BMA GMA or RWA 17 6 5 Key switch SCT221 SCT to temporary unlocking 17 6 6 Key switch SCT320 for external control unlocking locking temporary unlocking and acknowledging alarms 17...

Page 3: ...s along escape routes should be inspected annually by a specialist The specialist X X must issue a certificate verifying the periodic inspection which the owner must submit to the building inspec tora...

Page 4: ...ding to VDE 0833 surface mounted cables in steel conduit For flush mounted cabling flush mounted sockets depth 62 5 mm at a mounting height of 850 mm from upper edge of floor and up to 1200 mm for the...

Page 5: ...ation and assembly Fit the terminal blocks to the back of the door control unit X X Fit jumpers according to the terminal diagram X X Fit the door control unit X X Fit the green adhesive frame X X Tes...

Page 6: ...ht of emergency button 850 mm 1200 mm from floor X X surface 850 1200 Take off the mains connection cover X X Connect the 230 V cable to the screw terminals of the PSU and refit the cover X X Connect...

Page 7: ...inder 40 mm 30 10 Eight way adjustable When the plant is in operation set it into service X X mode To do this turn key to left for ten seconds Right LED lights up green Take housing off the wall brack...

Page 8: ...e any action for three minutes or in the Service menu select End service mode X X The door control unit is then in its normal state again Connecting service terminal ST220 with door control unit 4 2 3...

Page 9: ...is locked again automatically and the pre alarm is reset Door alarm 4 4 5 If the pre alarm time is exceeded the door alarm is triggered This must then be reset with the built in key switch or with a n...

Page 10: ...t for about one second X X LED 1 lights up green The door is unlocked Locking the door When the system is unlocked the locking elements are enabled and the door can not be be opened Turn the key to th...

Page 11: ...e emergency button to the right X X The emergency button returns to its normal state Refit the cover X X Acknowledge the alarm X X Acknowledge alarm 5 3 2 Precondition The alarm cause has been elimina...

Page 12: ...d twice Bus system address assigned more than once Change CAN address X X Invalid date time Invalid date or time value Correct data in service menu X X Reading out alarm messages 5 5 Misuse of the sys...

Page 13: ...ugh built in emergency button Reset door control unit emergency X X button SK failed NT opener failed NC contact of built in emergency button failed Locking element not connected Rectify fault X X Che...

Page 14: ...us communication 45 CAN L GEZE bus communication 42 RS485 A communication with KL220 TAN220 41 RS485 B communication with KL220 TAN220 X105 Black terminal field 2 24 V DC 12 Key switch lock temporary...

Page 15: ...they are connected with reversed polarity the controller can become damaged If the controller s relay chatters and the LEDs are flashing on and off isolate the door control unit from the mains immedi...

Page 16: ...s 41 RS485 B X107 green terminal strip 24VDC 2 Directunlocking 7 1 GND 8 Indirectunlocking Powersupplyunit Screwterminal X102 PlugforGEZE keyswitchor BK RD RD BN BU 6A 2 1 BN BU L1 N GN YE PE 4 5 NO C...

Page 17: ...contact for unlocking set the input to High Active Key switch SCT221 SCT to temporary unlocking 6 5 Brief unlocking input 24 V DC orange terminal strip SCT No 117996 024467 UP AS500 SCT No 117996 0244...

Page 18: ...ing Doorclosed 24VDC Input1 short termrelease 24VDC Input3 firealarmsystem Input2 short termrelease Temporary unlocking through button key switch Access control Door contact Powersupplyunit Ribboncabl...

Page 19: ...h is working correctly Locking through key switch is working correctly Forced locking through EMA working Feedback from magnet and or door opener working correctly Additional door contacts working cor...

Page 20: ...est H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla C Comerc 2 22 Nave 12 08980 Sant Feliu de Llobregat Barcelona Tel 34 0 9 02194036...

Reviews: