Input- Manual Dimming (n.6)
This object is used to adjust the brightness.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 3.007 DPT_Control_Dimming.
The standard format of the object is
4 bit and the information it contains is
“increase %
/decrease
%”.
Input- Follow-up time in minute (n.7)
This object is used to set the follow-up time.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 7.006 DPT_TimePeriodMin.
The standard format of the object is
2 byte and the information it contains is
“
VALUE
(min)
”.
Input- Overwrite threshold 1 (n.8)
This object is used to overwrite threshold 1.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 9.004 DPT_Value_Lux.
The standard format of the object is
2 byte and the information it contains is
“VALUE
(lux)”.
Toggle threshold 1 and 2 (n.9)
This object is used to switch between threshold 1 and 2. .
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.003 DPT_Value.
The standard format of the object is
1 bit and the information it contains is
“enable/disable”.
Input- Switch set value and fixed value (n.10)
This object is used to set a value fixed brigthness.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.003 DPT_Value.
The standard format of the object is
1 bit and the information it contains is
“enable/disable”.
Input- Start/Stop burn-in function (n.11)
This object is used to start or stop the Burn-in function.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.010 DPT_Start.
The standard format of the object is
1 bit and the information it contains is
“Start/Stop”.
Input- Retrieve burn-in time (n.12)
This object is used to trigger the spontaneous sending of the remaining burn-in time
that is sent through the object
“Output- burn-in time status” (n.19)
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.010 DPT_Start.
The standard format of the object is 1 bit and the information it contains is
“Start/Stop”.
Summary of Contents for CHORUS GWA9531
Page 7: ...7 ...
Page 14: ...14 ...
Page 15: ...15 Regulation mode ...
Page 34: ...34 ...
Page 38: ...38 ...
Page 42: ...42 ...
Page 45: ...45 ...
Page 46: ...46 9 COMMUNICATION OBJECTS ...