15
Tools
n
Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680-1.
n
Screwdriver for cross head screws, size 2.
Note
n
Connect screen only to the respective terminals and to the central earthing point
(CEP).
n
The rated voltage is indicated on the name plate.
n
When switching off inductive loads, voltage spikes are produced that may impair the
operation of control and measuring systems.
Connected contactors must therefore be provided with suppressors such as
RC combinations.
Electrical Connection
- continued -
Basic Settings
Factory setting
Control unit TRS 5-40
The control unit features the following factory set default values:
n
Node ID: 95
n
Baud rate: 250 kBit/s (125 m cable length)
n
Configuration: Measuring channels 1 and 2 energised, measuring channel 1:
MAX limit, measuring channel 2: MIN limit.