17
Commissioning
- continued -
Changing configuration
- continued -
5. Apply mains voltage.
The green LED “Power” is illuminated: The modified configuration has been accepted.
6. The red LED “Bus status” is illuminated. The new configuration has not been accepted.
Repeat the setting or replace the control unit.
7. Switch off mains voltage. Set the original node ID and baud rate.
8. Re-attach terminal strip
B
and fasten fixing screws. Apply mains voltage, the control unit TRS 5-40
works now with the new configuration.