Install the SRL 6-60 monitoring logic unit as close as possible to the external level pot.
The field housing of the monitoring logic unit is intended for wall mounting. The four holes can be ac-
cessed by removing the upper part of the housing.
The dimensions of the holes are stamped on the back of the housing.
Danger of death from penetrating water due to short circuits and electric shock.
Leaky housing seals and incorrect or faulty cable glands can allow water to penetrate, leading
to a short circuit.
■
■
Check and clean the housing lid seal before closing the lid.
■
■
Only use the intended seal for the cable gland. Replace faulty seals and cable glands.
If the unit is to be installed outdoors, outside the protection of a building, environmental
influences may adversely affect function.
■
■
Pay attention to the admissible ambient conditions in the technical data,
“Admissible ambient conditions” on page 16.
■
■
Do not operate the equipment if the temperature is below freezing.
■
◆
At temperatures below freezing, use a suitable heat source (e.g. control cabinet heater,
etc.).
■
■
Connect all system parts to a central earthing point to prevent equalisation currents.
■
■
Use a cover to protect the equipment from direct sunlight, condensation and heavy rain.
■
■
Use UV-resistant cable ducts for routing the connecting cable.
■
■
Take further measures to protect the unit from lightning, insects and animals, and salty air.