SRL 6-60 - Installation & Operating Manual -
819698-00
Start, operation, alarm and test
Stop
If the standby time or purge time is exceeded, the
monitoring logic unit notifies the URS 60 / URS
61 safety control unit via CAN bus and the safety
circuit is opened.
Display after the shut-off (opening) of the
safety circuit
■
■
STOP - flashing
Additional monitoring of the purge time
on the URS 60 / URS 61 safety control unit
At the same time, the URS 60 / URS 61 safety
control unit monitors the purge time as a
safety-relevant function, and opens the safety
circuit if it is exceeded.
When is the interruption of the
safety circuit cancelled again?
Interruption and the STOP signal are only can-
celled after the purging process has successfully
taken place.
Cancelling the locking of the safety circuit
Interrupting the safety circuit shuts it off and
locks it for heating. This lock therefore has to be
cancelled after the purging process.