16
Electrical Connection
Control cable
NRS, NRR, LRR, TRS, URB 1
To wire the equipment, screened multicore twistedpair control cable
must
be used for the bus line, e.
g. UNITRONIC
®
BUS CAN 2 x 2 x ... mm
2
or RE2YCYVfl 2 x 2 x ... mm
2
.
Control cable assemblies (2 x 2 x 0.32 mm² cable with plug and connector) of various lengths are
available as addon equipment.
NRG, LRG, EF, URZ, TRV, URB 2
The equipment is fitted with sensor plugin connectors (5 poles, Acoded). For connecting the bus
devices control cable assemblies (with plug and connector) of various lengths are available as addon
equipment.
Note that the recommended control cables are not UVresistant and must be protected by a
UVresistant plastic tube or cable duct if the equipment is installed outdoors (except for URB 2).
The baud rate (data transfer rate) dictates the cable length and size between the bus nodes. The total
power consumption must also be taken into consideration when selecting the conductor size. The total
power consumption is obtained from the number of bus nodes.
If the cable length between the steam boiler and the control cabinet exceeds 15 m, we recommend that
you fit a branching box that is resistant to electromagnetic interference (stock code 1501214) and use
a control cable with a larger conductor size for the distance to the control cabinet.
S 8
S 9
S 10
Baud rate
Cable length
Number of pairs
and conductor size [mm
2
]
OFF
ON
OFF
250 kBit/s
125 m
2 x 2 x 0.32
Factory setting
ON
ON
OFF
125 kBit/s
250 m
2 x 2 x 0.5
OFF
OFF
ON
100 kBit/s
335 m
2 x 2 x 0.75
ON
OFF
ON
50 kBit/s
500 m
on request, depending on
bus configuration
OFF
ON
ON
20 kBit/s
1000 m
ON
ON
ON
10 kBit/s
1000 m
Set baud rate via code switch
9
. Make sure that all bus nodes feature the same settings.
UNITRONIC
®
is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.
Summary of Contents for NRS 1-41
Page 1: ...1 E N English Level Switch NRS 1 41 Original Installation Instructions 810830 04 ...
Page 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Page 11: ...11 Design Fig 3 0 NRS 1 41 0 ...
Page 12: ...12 Functional Elements NRS 1 41 Fig 5 Fig 4 1 7 6 5 4 3 2 8 9 ...
Page 15: ...15 Installation continued Fig 6 Example of installation 0 0 Fig 7 20 20 ...
Page 35: ...35 For your Notes ...