25
NRS 141
Apply power to the unit.
The four status LEDs flash rapidly.
The LED “Power” lights up.
The test cycle takes about 3 sec.
NRS 141
Normal operation, electrode exposed.
The four indicator LEDs are not illuminated.
The LED “Power” lights up.
Note
n
To analyse and eliminate malfunctions that may occur during the commissioning
procedure refer to section
“System Malfunctions”
.
Commissioning
Operation
NRS 141
Press button briefly (1 s).
The test mode is activated for about 10 sec.
Be sure to press button or within
these 10 sec.
Note:
The control circuit will be interrupted during
the test cycle.
Press button for 3 sec
.
LED 1 flashes rapidly and remains permanently
illuminated after 3 sec.
A highlevel alarm is simulated for level
electrode 1.
Test Cycle