Scope of supply
NRS 141
1 Level switch NRS 141 (plugin unit in plastic case with terminals)
1 Terminating resistor 120 Ω
1 Installation manual
Description
The switching controller type NRS 141 is a selfmonitoring highwater level limiter with periodic self
checking and monitoring feature of the output relay contacts designed to be used in conjunction
with
one
level electrode type NRG 1641, 1741 or 1941. The switching controller has the following
function:
n
Highwater level alarm with
one
level electrode
The equipment detects the max. water level (highlevel limiter) and complies with the German regula
tions for use in steam and hotwater plants operating without constant supervision according to
TRD 604, sheets 1 and 2 (24/72 hrs operation) as well as DIN EN 12952 and DIN EN 12953.
This item of electrical equipment complies with the Technical Regulations on Protection Circuits
DIN EN 501561.
The level data are transferred from the electrode NRG 1…41 to the switching controller via CAN bus
using the CANopen protocol. Only
one
highlevel limiting system may be used per CANbased network.
Explanatory Notes
Function
At regular intervals the level electrode NRG 1…41 sends a data telegram to the switching controller
NRS 141. The data transfer is effected by means of a CAN bus according to ISO 11898. The transferred
measuring data are constantly evaluated by the controller. A periodic selfchecking routine tests every
3 seconds the integrity of the system and its safety functions, with a malfunction in the switching
controller resulting in immediate boiler shutdown. When the CAN bus line and, consequently, the data
transmitting cycle are interrupted, the controller sends a visual signal to indicate a faulty condition and
the relays are instantaneously deenergized (failsafe position).
The switching controller also facilitates userfriendly performance tests and detection/evaluation of
malfunctions.
To guarantee the correct and safe functioning of the highlevel limiter a min. electrical conductivity of
0.5
µ
S/cm at 25 °C is required.
The relay deenergizing delay is normally set to 3 seconds at the factory but delays of 15 to 25 seconds
are available on request.
Apart from the burner protection circuit there is also a separate PhotoMOS make contact output for
remote indication.
The automatic selftesting routine of the switching controllers checks every 3 seconds their safety
functions. The corresponding functions of the level electrodes will be tested by the electrode’s self
checking routine every 10 sec. The malfunction information is updated with every selftest. If no faults
have occurred the malfunction information will be deleted automatically. If faults persist the malfunction
information remains stored. If a malfunction is detected, the signal output of the control unit (terminal 7
and 8) is opened and closed in a clock pulse controlled way. As part of the automatic selftesting routine
of the switchting controller, the switchingoff of the output relays every 6 hrs is checked, too.
Summary of Contents for NRS 1-41
Page 1: ...1 E N English Level Switch NRS 1 41 Original Installation Instructions 810830 04 ...
Page 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Page 11: ...11 Design Fig 3 0 NRS 1 41 0 ...
Page 12: ...12 Functional Elements NRS 1 41 Fig 5 Fig 4 1 7 6 5 4 3 2 8 9 ...
Page 15: ...15 Installation continued Fig 6 Example of installation 0 0 Fig 7 20 20 ...
Page 35: ...35 For your Notes ...