Technical data
Supply voltage
■
■
24 V DC +/-20 %
Power consumption
■
■
max. 5 VA
Current input
■
■
max. 0.3 A
Required external fuse
■
■
0.5 A M
Input/output
■
■
Interface for CAN bus to ISO 11898, CANopen, insulated
Inputs NRR 2-60
■
■
1 x analogue input for potentiometer 0 - 1000
W
, two-wire connection (indication of valve position)
■
■
1 x analogue input IN 2, 4 - 20 mA (feedwater quantity) - (option)
■
■
1 x analogue input IN 3, 4 - 20 mA (steam quantity) - (option)
Outputs of MIN/MAX contacts
■
■
2 x potential-free changeover contacts (changeover relays), contact material AgNi0.15, AgSnO2
■
■
Maximum switching current - 8 A at 250 V AC / 30 V DC - cos
ϕ
= 1
■
■
Inductive loads must have interference suppression (RC combination) as per the manufacturer's
specification
Off delay of MIN/MAX output relays
■
■
Factory default setting 3 seconds.
Outputs of control valve OPEN/CLOSED
■
■
2 x potential-free changeover contacts (changeover relays), contact material AgNi0.15, AgSnO2
■
■
Maximum switching current - 8 A at 250 V AC / 30 V DC - cos
ϕ
= 1
■
■
Inductive loads must have interference suppression (RC combination) as per the manufacturer's
specification
Analogue output
■
■
1 x actual value output 4 - 20 mA, e.g. for an actual value display
■
■
Max. load resistance 500
W