Factory settings
The level controller is delivered with the following factory default settings:
■
■
Baud rate:
50 kBit/s (max. cable length 1000 m)
■
■
Controller group:
1
■
■
Code switch setting:
Sliding switch, white (1 to 4 = OFF)
Configuring the controller group and baud rate,
see page 23, Fig. 10.
■
■
MAX switchpoint:
80 %
■
■
MIN switchpoint:
20 %
■
■
Setpoint:
50% of measuring range
■
■
Direction of corrective action: Inlet control
■
■
Proportional band (Pb):
± 20 % of setpoint
■
■
Reset time (Ti):
0 seconds
■
■
Neutral band:
± 5 % of setpoint
■
■
Valve runtime:
40 seconds
■
■
MIN/MAX alarm
off delay:
3 seconds (factory set)
■
■
Quality factor:
1.00 (3-component control)