LO
9.25
pH
HI
4.55
pH
0
pH
14
pH
max. pulses (0-120 pulses/minute)
Relay 4
Deviation= 9.45
Relay 3
Deviation= 9.25
LO
5.30
pH
HI
7.50
pH
0
pH
14
pH
Correct
max. pulses (0-120 pulses/minute)
Relay 4
Deviation=
3.50 pH
Relay 3
Deviation=
5.30 pH
11.00
pH
LO and HI
7.30 pH
0
pH
14
pH
max. pulses (0-120 pulses/minute)
Relay 4
Deviation=
4.90 pH
Relay 3
Deviation=
5.20 pH
12.20
pH
2.10
pH
Correct
INCORRECT
16
The dual proportional relay configuration is
primarily designed to control external metering
pumps. Setpoints, deviation ranges, and maxi-
mum pulse rates are selected via the relay menu.
• Setpoint: pH value at which relay pulsing be-
gins. Relay 3 setpoint must be less than or
equal to relay 4 setpoint.
• Deviation: Number of pH units from setpoint to
maximum pulse rate. Deviation values cannot
extend beyond the 0 to 14 pH scale.
• Pulse Rate: Pulse rate selected from 0 to 120
pulses per minute maximum.
Figure 10
Dual Proportional relay
examples
Note:
Relay 3 setpoint
cannot exceed relay 4
setpoint