Abnormal
Description & Checkpoint
Solution
(11)
Transferring
failure
between
reserve and
inverter.
DC BUS voltage becomes abnormal
during transferring. DCV value can be
read in LCD menu.
Take out the P&P module 2
and make sure the SCR
drive connection is OK.
3P PCB has problem.
Refer to PCB LED
Detecting Guide. Take out
the P&P module 2 and
check the 3P PCB.
LED A4(OTF) in the 3A PCB lights.
Refer to PCB LED
Detecting Guide and check
the 3G PCB.
In P&P modules, the temperature sensor
Take out the P&P module
sockets on 3G/3P PCB and hest sink are
and connect them properly.
not connected properly. WARNING LED
of FUSE/TEMP still illuminates.
Phase sequence error of output
Change the transformer
transformer.
wiring.
If the abnormal cannot be improved as the
Refer to PCB LED
aforesaid solution action has been taken.
Detecting Guide and check
the 3G and 3P PCB.
(12) Phase lack
when AC
output.
The mimic output LED in the front panel
blinks.
Make sure the signal sockets
in 3T PCB are connected
properly.
Fuse has blown in 3T PCB
Replace the fuse.
If the abnormal cannot be corrected after
Refer to PCB LED
the solution actions have been taken.
Detecting Guide and check
the 3T PCB.
(13) The
mimic battery
LED in the
front panel
blinks.
Batteries become worn out or damaged.
Replace batteries.
9-5
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......