PHASE SHIFT
AC
DC
INPUT
RECTIFIER
BREAKER
INDUCTOR
CAPACITOR
SCR
OUTPUT
SCR
TRANSFORMER
12-PULS E FULL CONTRO L RECTIFIER
In order to further improve the power factor and reduce harmonic current drawn by the
rectifier, UPS at 100KVA and above, use the 12-pulse full controlled rectifier. The total
current harmonic current can be reduced to around 15%, and power factor improved to
over 0.8. A phase shift transformer is added to achieve this performance. The input
inductor is retained also to obtain the best result. Although this results in higher cost,
the unit is much more reliable and rugged. Users do not need to increase the input
breaker and cable sizes, since input KVA and harmonic current drawn is minimized,
fulfilling the worldwide energy saving requirements.
The harmonic current can be further lowered by adding harmonic filters (factory
installation available). The total harmonic current can be reduced to approximately 9%.
Another alternative method to reduce the harmonic current (especially for very large
KVA UPS) is to employ 18-pulse full controlled rectifier (available as an option). The
total harmonic current can be reduced to approximately 7%.
1-9
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......