6
Subject to technical modifications of Optima 100
To return to the main display, press button B4 repeatedly
until all of the LED’s stop flashing.
Level 2 inlet airflow
Level 2 inlet airflow is to be adjusted to match the level 2
outlet airflow.
To access level 2 from the main display, hold down button
B3 for more than 10 seconds until LED D1 begins to flash.
Press button B4 four times more until LED D2/D5 begin to
flash at the same time. Inlet airflow can now be set to level
2.
If you are already in the ventilator settings menu, just
press B4 repeatedly until LED D2/D5 begin flashing at the
same time.
Each press of B3 decreases the level 2 inlet airflow by 1%.
Each press of B5 increases the level 2 inlet airflow by 1%.
To return to the main display, press button B4 repeatedly
until all of the LED’s stop flashing.
Level 3 inlet airflow
Level 3 inlet airflow is to be adjusted to match the level 3
outlet airflow.
To access level 3 from the main display, hold down button
B3 for more than 10 seconds until LED D1 begins to flash.
Press button B4 five times more until LED D3/D5 begin to
flash at the same time. Inlet airflow can now be set to level
3.
If you are already in the ventilator settings menu, just
press B4 repeatedly until LED D3/D5 begin flashing at the
same time. Inlet airflow can now be set to level 3.
Each press of B3 decreases the level 3 inlet airflow by 1%.
Each press of B5 increases the level 3 inlet airflow by 1%.
To return to the main display, press button B4 repeatedly
until all of the LED’s stop flashing.
3.3 Filteralarm
A built-in filter timer measures the amount of time the unit
has operated since the last filter replacement.
The filter timer can be set between 1-6, which corresponds
with 1-6 months. It is recommended to initially set the filter
timer to 3, corresponding to 3 months.
If the filters become too dirty during the set period, you
can set the filter timer to a lower number of months.
On the other hand, if the filters do not require replacement
at the end of the set period, you can set the filter timer to a
higher number of months.
When the filter timer reaches the set period for a filter
change, LED D5 will begin to flash. When the filters are
changed, the alarm is reset by holding button B4 down for
more than 10 seconds, until LED D5 switches off.
The filter timer is set as described below.
1 month
Hold the button B4 down for more than 10 seconds, until
LED D1 begins to flash.
Then press button B4 to confirm the setting and to return
to the main display.
2 months
Hold the button B4 down for more than 10 seconds, until
LED D1 begins to flash.
Then press button B5 once until LED D2 begins to flash.
Then press button B4 to confirm the setting and to return
to the main display.
3 months
Hold the button B4 down for more than 10 seconds, until
LED D1 begins to flash.
Then press button B5 twice until LED D3 begins to flash.
Then press button B4 to confirm the setting and to return
to the main display.
4 months
Hold the button B4 down for more than 10 seconds, until
LED D1 begins to flash.
Then press button B5 three times until LED D4 begins to
flash. Then press button B4 to confirm the setting and to
return to the main display.
5 months
Hold the button B4 down for more than 10 seconds, until
LED D1 begins to flash.
Then press button B5 four times until LED D1/D5 begin to
flash. Then press button B4 to confirm the setting and to
return to the main display.