Genvex Optima 100 Design Operating Instructions Manual Download Page 5

5

Subject to technical modifications of Optima 100

3.2 Ventilator Speed

Both ventilators can be set independently of each other, 

so that the airflow at the inlet and outlet are equal, which 

results in optimal operation. Commissioning of the unit 

must be carried out using technical equipment for and 

may be done without the use of a main regulating damper. 

It is not advised to set the airflow without expert help and 

guidance. Incorrect settings can result in increased energy 

use.

You must manually select the ventilation unit’s operating 

level. You can select this with a short press of the button 

B3. 

Choose the ventilation speed:

Level 0 inlet/outlet airflow: LEDs off – 

Standby – cannot be set via the display

Level 1 inlet/outlet airflow: LED D1 on –

Default 25% (can be changed, see below)

Level 2 inlet/outlet airflow: LED D2 on – 

Default 50% (can be changed, see below)

Level 3 inlet/outlet airflow: LED D3 on –

Default 75% (can be changed, see below)

Level 4 inlet/outlet airflow: LED D4 on –

Always operated at 100% and cannot be set

By default the system is always operating. If the unit is to 

be set to Standby, it can only be done via a data logger. 

Alternatively, the unit can be switched off at the main 

switch.

The procedure for setting the ventilator speed to level 

1, 2 and 3 is described below. If no button is activated 

within 100 seconds in the set-up menu, the control system 

automatically returns to the main display.

Level 1 outlet airflow

Level 1 is the lowest speed. This is often used with no-one 

is at home.

To access level 1 from the main display, hold down button 

B3 for more than 10 seconds until LED D1 begins to flash. 

Outlet airflow can now be set to level 1.

If you are already in the ventilator settings menu, just 

press B4 repeatedly until LED D1 begins flashing.

Each press of B3 decreases the outlet airflow by 1%.

Each press of B5 increases the outlet airflow by 1%.

To return to the main display, press button B4 repeatedly 

until all of the LED’s stop flashing.

Level 2 outlet airflow

Level 2 is the recommended operating level for an optimal 

indoor climate and should be commissioned to meet the 

building’s ventilation requirements.

To access level 2 from the main display, hold down button 

B3 for more than 10 seconds until LED D1 begins to flash. 

Press button B4 once more until LED D2 begins flashing. 

Outlet airflow can now be set to level 2.

If you are already in the ventilator settings menu, just 

press B4 repeatedly until LED D2 begins flashing.

Each press of B3 decreases the level 2 outlet airflow by 

1%.

Each press of B5 increases the level 2 outlet airflow by 

1%.

To return to the main display, press button B4 repeatedly 

until all of the LED’s stop flashing.

Level 3 outlet airflow

Level 3 is the highest speed that can be set. It is typically 

used when there are a lot of people, or there is a lot of 

activity in the kitchen.

To access level 3 from the main display, hold down button 

B3 for more than 10 seconds until LED D1 begins to flash. 

Press button B4 twice more until LED D3 begins flashing. 

Outlet airflow can now be set to level 3.

If you are already in the ventilator settings, just press B4 

repeatedly until LED D3 begins flashing.

Each press of B3 decreases the level 3 outlet airflow by 

1%.

Each press of B5 increases the level 3 outlet airflow by 

1%.

To return to the main display, press button B4 repeatedly 

until all of the LED’s stop flashing.

Sucking out

Level 1 inlet airflow

Level 1 inlet airflow is to be adjusted to match the level 1 

outlet airflow.

To access level 1 from the main display, hold down button 

B3 for more than 10 seconds until LED D1 begins to flash. 

Press button B4 three times more until LED D1/D5 begin 

to flash at the same time. Inlet airflow can now be set to 

level 1.

If you are already in the ventilator settings menu, just 

press B4 repeatedly until LED D1/D5 begin flashing at the  

same time.

Each press of B3 decreases the inlet airflow by 1%.

Each press of B5 increases the inlet airflow by 1%.

Summary of Contents for Optima 100 Design

Page 1: ...Genvex A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www genvex dk O R IGIN A L w w w genvex d k Optima 100 Opus Optima 100 Design Version 2012 02 28 Operating instructions uK ...

Page 2: ...3 Operation 5 3 1 Use and changing of the settings 5 3 2 Ventilator Speed 5 3 3 Filter alarm 6 3 4 Bypass 7 3 5 Electrical Heating 7 3 6 Restoring the factory settings 8 3 7 Set points table 8 4 Function 8 4 1 Extra capacity 8 5 Maintenance 9 5 1 Parts 9 5 2 Alarms 9 5 3 Demounting taking the system out of operation 9 6 Troubleshooting 10 6 1 System does not operate 10 6 2 Fault on the air side 10...

Page 3: ...int Support Point Underneath the control panel there is an access for the A Terminal block Connection to main circuit board A low current cable 8 x 0 25 mm2 must be attached between the unit and the control panel 50 m is the maximum cable length The voltage drop for cable lengths over 50 m is too high and can result in unreliable operation How to mount the wall fixture First screw the fixture secu...

Page 4: ...d to hold both buttons down i e B3 and B5 together 3 Operation All Genvex GE S Energy and GEU residential ventilation units can be operated with the Optima 100 control The Optima 100 control has the following settings Ventilator speed filter alarm bypass ON OFF and electrical heating ON OFF The control unit is supplied with factory set settings that enable the unit to be operated without initially...

Page 5: ...1 To return to the main display press button B4 repeatedly until all of the LED s stop flashing Level 2 outlet airflow Level 2 is the recommended operating level for an optimal indoor climate and should be commissioned to meet the building s ventilation requirements To access level 2 from the main display hold down button B3 for more than 10 seconds until LED D1 begins to flash Press button B4 onc...

Page 6: ...e unit has operated since the last filter replacement The filter timer can be set between 1 6 which corresponds with 1 6 months It is recommended to initially set the filter timer to 3 corresponding to 3 months If the filters become too dirty during the set period you can set the filter timer to a lower number of months On the other hand if the filters do not require replacement at the end of the ...

Page 7: ...ing element further heats the inlet air after it has been heated via the heat recovery process in the system The heating element must be activated manually via the display This is done as per the following To activate the menu hold the button B5 down for more than 10 seconds until LED D1 begins to flash or the LEDs D1 D2 flash at the same time Electrical heating ON LEDs D1 D2 flash at the same tim...

Page 8: ...utlet must be checked for blockages and the water trap must be checked for water in association with changing filters before autumn begins Pour 1 liter of water in the condensation water tray and see if the water drains freely If the condensation outlet does not work there is a risk of water damage in the building Ventilators Remember to turn off the power before inspecting the unit The fan impell...

Page 9: ... condensation on the ground due to frost The outlet is not sufficiently protected against frost 6 2 Fault on the air side No inlet air to residence s rooms Fault Defective ventilator Blocked filter Dirt and leaves in the fresh air vent in Autumn or snow and ice in Winter Control circuit fuse has blown No outlet air from wet rooms Fault Defective ventilator Blocked filter Exhaust vent roof cap is b...

Page 10: ... Green Brown Brown Blue Blue Blue Blue Blue Yellow Yellow Yellow Red 5V GND 5V 1 2 1 2 L1 1 2 3 1 2 3 1 2 3 4 1 2 3 4 L2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 L3 1 2 1 2 H1 1 2 1 2 H3 1 2 1 2 H7 1 2 3 1 2 3 H8 1 2 1 2 H9 L1 M1 M2 M4 N PE PE PE T1 90 C manu PE PE L L N N PE PE T4 T9 M1 M2 1 2 3 4 1 2 3 4 L6 1 5 6 7 8 5 6 7 8 L6 2 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 4 4 4 4 5 5 5 6 6 7 7 8 8...

Page 11: ...11 Subject to technical modifications of Optima 100 ...

Page 12: ...ium Artiklima bvba B 9220 Hamme Tel 32 0 52 41 25 41 Fax 32 0 52 41 29 66 E Mail info artiklima be Ireland ECO Systems Ireland Ltd Co Antrim BT54 6PH Tel UK 028 ROI 048 44 2076 8708 Fax UK 028 ROI 048 44 2076 9781 E Mail info ecosystemsireland com Croatia Pichler CO d o o 10000 Zagreb Tel 385 0 1 65 45 407 Fax 385 0 1 65 45 409 E Mail pichler zg hnet hr Slovenia Pichler CO d o o 2000 Maribor Tel 3...

Reviews: