Genvex Optima 100 Design Operating Instructions Manual Download Page 3

3

Subject to technical modifications of Optima 100

1. Mounting Design

1.1 Installation of the control panel

The control panel is designed to be mounted onto a flat 

wall.

1.2 Mounting

Find the location on the wall where you will fix the control 

panel and mark the screw-hole positions. A min. of four 

screws must be used, the two bottommost and the two 

topmost.

Mandatory Screw

Mandatory Screw

Mandatory Screw

Mandatory Screw

Screw

Screw

Hold the wall frame against the wall and mark the 

screw-hole positions. Drilling of holes, hole size and the 

corresponding screws for fixing the panel depend on the 

wall material.

Place the control panel in the fixtures and tilt it in against 

the wall. The four support points in the corner of the 

display must touch the wall to keep the display stable.

A

Support 

 

Point

Support 

 

Point

Support 

 

Point

Support 

 

Point

Underneath the control panel there is an access for the:

A:  Terminal block. Connection to main circuit board

A low-current cable 8 x 0.25 mm2 must be attached 

between the unit and the control panel. 50 m is the 

maximum cable length. The voltage drop for cable 

lengths over 50 m is too high and can result in unreliable 

operation.

How to mount the wall fixture:

First screw the fixture securely onto the flat wall and pass 

the cable up from below.

Connect the low-current cable to the terminal block. Check 

that the cable is connected to the same numbers at both 

ends. (Between the control panel and the main circuit 

board in the unit.)

Next clip the control panel to the wall fixture by guiding 

it down from above, slightly slanting out at the bottom. 

Finish by pressing in at the bottom so that it sits flat 

against the wall. For demounting: pull the control panel a 

little out at the bottom and lift up.

Pos.

Description

1

Panel housing

2

Front of panel

3

Pressure plate for display

4

Wall fixture

5

Glass for the display

Summary of Contents for Optima 100 Design

Page 1: ...Genvex A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www genvex dk O R IGIN A L w w w genvex d k Optima 100 Opus Optima 100 Design Version 2012 02 28 Operating instructions uK ...

Page 2: ...3 Operation 5 3 1 Use and changing of the settings 5 3 2 Ventilator Speed 5 3 3 Filter alarm 6 3 4 Bypass 7 3 5 Electrical Heating 7 3 6 Restoring the factory settings 8 3 7 Set points table 8 4 Function 8 4 1 Extra capacity 8 5 Maintenance 9 5 1 Parts 9 5 2 Alarms 9 5 3 Demounting taking the system out of operation 9 6 Troubleshooting 10 6 1 System does not operate 10 6 2 Fault on the air side 10...

Page 3: ...int Support Point Underneath the control panel there is an access for the A Terminal block Connection to main circuit board A low current cable 8 x 0 25 mm2 must be attached between the unit and the control panel 50 m is the maximum cable length The voltage drop for cable lengths over 50 m is too high and can result in unreliable operation How to mount the wall fixture First screw the fixture secu...

Page 4: ...d to hold both buttons down i e B3 and B5 together 3 Operation All Genvex GE S Energy and GEU residential ventilation units can be operated with the Optima 100 control The Optima 100 control has the following settings Ventilator speed filter alarm bypass ON OFF and electrical heating ON OFF The control unit is supplied with factory set settings that enable the unit to be operated without initially...

Page 5: ...1 To return to the main display press button B4 repeatedly until all of the LED s stop flashing Level 2 outlet airflow Level 2 is the recommended operating level for an optimal indoor climate and should be commissioned to meet the building s ventilation requirements To access level 2 from the main display hold down button B3 for more than 10 seconds until LED D1 begins to flash Press button B4 onc...

Page 6: ...e unit has operated since the last filter replacement The filter timer can be set between 1 6 which corresponds with 1 6 months It is recommended to initially set the filter timer to 3 corresponding to 3 months If the filters become too dirty during the set period you can set the filter timer to a lower number of months On the other hand if the filters do not require replacement at the end of the ...

Page 7: ...ing element further heats the inlet air after it has been heated via the heat recovery process in the system The heating element must be activated manually via the display This is done as per the following To activate the menu hold the button B5 down for more than 10 seconds until LED D1 begins to flash or the LEDs D1 D2 flash at the same time Electrical heating ON LEDs D1 D2 flash at the same tim...

Page 8: ...utlet must be checked for blockages and the water trap must be checked for water in association with changing filters before autumn begins Pour 1 liter of water in the condensation water tray and see if the water drains freely If the condensation outlet does not work there is a risk of water damage in the building Ventilators Remember to turn off the power before inspecting the unit The fan impell...

Page 9: ... condensation on the ground due to frost The outlet is not sufficiently protected against frost 6 2 Fault on the air side No inlet air to residence s rooms Fault Defective ventilator Blocked filter Dirt and leaves in the fresh air vent in Autumn or snow and ice in Winter Control circuit fuse has blown No outlet air from wet rooms Fault Defective ventilator Blocked filter Exhaust vent roof cap is b...

Page 10: ... Green Brown Brown Blue Blue Blue Blue Blue Yellow Yellow Yellow Red 5V GND 5V 1 2 1 2 L1 1 2 3 1 2 3 1 2 3 4 1 2 3 4 L2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 L3 1 2 1 2 H1 1 2 1 2 H3 1 2 1 2 H7 1 2 3 1 2 3 H8 1 2 1 2 H9 L1 M1 M2 M4 N PE PE PE T1 90 C manu PE PE L L N N PE PE T4 T9 M1 M2 1 2 3 4 1 2 3 4 L6 1 5 6 7 8 5 6 7 8 L6 2 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 4 4 4 4 5 5 5 6 6 7 7 8 8...

Page 11: ...11 Subject to technical modifications of Optima 100 ...

Page 12: ...ium Artiklima bvba B 9220 Hamme Tel 32 0 52 41 25 41 Fax 32 0 52 41 29 66 E Mail info artiklima be Ireland ECO Systems Ireland Ltd Co Antrim BT54 6PH Tel UK 028 ROI 048 44 2076 8708 Fax UK 028 ROI 048 44 2076 9781 E Mail info ecosystemsireland com Croatia Pichler CO d o o 10000 Zagreb Tel 385 0 1 65 45 407 Fax 385 0 1 65 45 409 E Mail pichler zg hnet hr Slovenia Pichler CO d o o 2000 Maribor Tel 3...

Reviews: