Genvex ECO 190 Operating Instructions Manual Download Page 17

 

 

 17

Follow the following instructions to achieve optimal 

performance:

Before you open the unit, turn off the power/

pull out the plug and wait until the fans have 

stopped completely.

A couple of days after the primary installation, check that 

the condensation outlet is working.

Environmental requirements

When repairing or dismantling the unit, statutory 

environmental regulations must be observed regarding 

recycling and destruction of various materials.

7.1 Unit

Filters

When the alarm flashes in the control panel display, the 

filters must be changed. Stop the system using the circuit 

breaker of the unit or the circuit breaker on the terminal 

board. Open the front cover/filter drawers and remove the 

filters. Once the filters are changed, reset the filter timer.

There is a danger of cuts from sharp edges.  

The edges must not be damaged.  

Vacuum cleaning or using pressurised air on the 

filters is not recommended as it can impair filter 

performance.

G4 = Standard filter

F5 = Fine filter

F7 = Pollen filter

Condensation drain:

When changing the filter in August/September, before the 

outside temperature falls to 5°C, check that the 

condensation drain is not blocked by dirt and make sure 

that there is water in the water trap. Pour 1 litre of water 

into the condensation tray and make sure that it runs off 

freely. If the condensation drain does not work, this could 

lead to water damage at your home.

Heat exchanger:

Inspect the heat exchanger every year. If it is dirty,  

remove it and:

•   Alu-exchanger: Wash in lukewarm soapy water and rinse 

using a hand shower, if necessary.

•   Plastic exchanger: No cleaning with solvents – use only 

clean water and carefully remove dust from air intake 

surfaces with a household vacuum cleaner.

 

Fans

Inspect the two fan wheels for dirt every year. If they are 

dirty, they can be washed with a brush, bottle cleaner, etc.

Supply air and extract air valves

Clean the valves by wiping them with a dry cloth.  

Make sure that the valves do not turn causing changes to 

the air volume.

7.2 Alarms 

Filter timer

The control has a filter timer to guarantee that the filter is 

changed and that optimal operation is achieved. When the 

timer reaches the set value, a key will flash in the display 

until the filters have been changed.

Once the filters are changed, press and hold down the filter 

indicator key until the diode switches off.

7.3 Dismantling/taking the system out of service

Do as follows:

Disconnect the power supply, i.e. the power cables. 

Disconnect the condensation outlet and power cables for 

any reheaters/preheaters. Disconnect the cables to the 

control panel and dismantle ducts. 

If the system should be taken out of service, the ducts must 

be dismantled to avoid condensed water in the system and 

in the ducts. Close all supply air and extract air valves.

7. MAINTENANCE

Summary of Contents for ECO 190

Page 1: ...OPERATING INSTRUCTIONS OPTIMA 260 ECO 190 ECO 375...

Page 2: ...TENTS 1 Installation of Optima 100 Design 3 2 Installation of Optima 100 Opus 4 3 Operation 5 4 Data Logger 5 5 Genlog Set Points 9 6 Function 16 7 Maintenance 17 8 Troubleshooting 18 9 Table of Facto...

Page 3: ...point Support point Underneath the control panel there is access for the A Terminal block Connection to main circuit board Fit a 8 x 0 25 mm2 low current cable between the unit and the control panel T...

Page 4: ...able between the ventilation unit print circuit board and the control panel The maximum cable length is 50 m The voltage drop for cable lengths over 50 m is too high and can cause operating errors Che...

Page 5: ...in order to take advantage of the automatic data logging feature The latest version of the Genvex Genlog software can be ordered from Genvex by telephone 45 73532700 1 2 3 4 K3 K5 All Genvex ventilati...

Page 6: ...seful if you want to refer to a certain logging There is an area with grey and white lines at the top of the logging area itself on the screen These lines will be red if relay function is active Hold...

Page 7: ...or monitoring only Data from Control System Set points in control system Opens the following box Here it is possible to retrieve all set points from the microchip or control panel change them and then...

Page 8: ...for the data logger General setup Here you can choose language model as well as folder for the log files For instance it can be a good idea to create a folder for logs under Documents and set up the p...

Page 9: ...ay These days can be filled in individually in the same way as under the example for Monday User menu 01 Temperature Set your desired temperature between 10 and 30 C Item 19 of the Service menu allows...

Page 10: ...or energy consumption or unpleasant indoor climate Setting option between 0 and 100 11 Level 2 Supply air Level 2 is the recommended speed of the system for providing optimal indoor climate It should...

Page 11: ...ith on off bypass e g ECO190 ECO 375 The bypass opens when the temperature reaches the set point in User Menu item 1 the temperature differential set in this menu item Setting option between 1 and 10...

Page 12: ...mper from opening at low outdoor air temperatures and from blowing cold unheated air into the dwelling use this function to configure the lowest outdoor air temperature at which the damper must be clo...

Page 13: ...n 1 25 13 35 Humidity regulating frequency Setting of desired frequency for how often the fan speed may be changed The function is defined as 1 per unit of time When humidity regulation is activated t...

Page 14: ...to maintain a supply temperature of 18 C 41 Reheat PI P P band for the PI controller for the electrical modulating reheater The P band controls the amplification of the controller following a deviati...

Page 15: ...rs Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3 4...

Page 16: ...sion For systems with electrical reheaters the reheater will connect when the temperature has fallen 1 C below the set temperature If the regulation time is set to e g 3 minutes temperature sensorT1 w...

Page 17: ...runs off freely If the condensation drain does not work this could lead to water damage at your home Heat exchanger Inspect the heat exchanger every year If it is dirty remove it and Alu exchanger Was...

Page 18: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Page 19: ...ing 3 C 15 0 C 21 Bypass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduction 0 C 0 10 C 25 Frost protection OFF ON OFF 26 Frost protection...

Page 20: ...t home and in society as a whole a Genvex system actually allows you to recover up to 95 of the heat energy All Genvex systems have energy label A An original Genvex system is built by skilled experie...

Reviews: