Genvex ECO 190 Operating Instructions Manual Download Page 11

 

 

 11

19 – Method of regulation

There are 2 options: 

0.  Cannot be used

1.  Supply air regulation (T1 sensor)

2.  Extract air regulation (T7 sensor)

If the system is used in a dwelling, supply air regulation is 

the normal choice. The set point is set to 1.  For extract air 

regulation, set the set point to 2.

Setting option: between 0 and 2

20 – Preheating

If preheating is set to ON in item 2 of the User Menu,  

the set point must be configured to the outdoor air 

temperature, at which the preheater should kick in. 

Setting option: between -15 and 0°C.

 

21 – Bypass open

Here you set the temperature at which the bypass should be 

100% open. You set a temperature differential, which 

means that if you want the bypass to be 100% open at e.g. 

23°C and if the set temperature in User Menu item 1 is 

20°C, this menu item should be set to 3°C. 

The bypass will open, provided that: 

1.  The extract air temperature is higher than the outdoor 

air temperature. 

2.  The outdoor air temperature is above the set 

temperature in Service Menu item 29. 

Units with modulating bypass

 

If the temperature rises by 0.5°C above the temperature 

set in User Menu item 1, the bypass damper will begin to 

open. The bypass is 100% open when the temperature 

reaches the set point in User Menu item 1 + the 

temperature differential set in this menu item. 

To get a smooth opening of the bypass, the temperature at 

which the bypass is fully open should be set to approx. 3 ºC 

above the set temperature in Use Menu item 1.

Units with on/off bypass (e.g. ECO190/ECO 375) 

 

The bypass opens when the temperature reaches the set 

point in User Menu item 1 + the temperature differential 

set in this menu item. 

Setting option: between 1 and 10°C.

22 – Regulation water

If a water reheater with a motor-operated valve is installed 

in the system, it may be necessary to adjust the regulation 

time.

The less regulation time, the faster the motor-operated 

valve will regulate.

Setting option: between 1 and 250 seconds.

23 – Regulation electricity

If an electrical preheater or an electrical reheater is 

installed, it may be necessary to adjust the regulation time. 

Setting option: between 1 and 300 minutes.

24 – Frost reduction

To avoid icing of the counter current heat exchanger,  

the supply air flow can be reduced gradually, once the 

discharge air temperature after the counter current  

heat exchanger has fallen below the set temperature.  

This function gradually reduces the supply air  

flow until the set value is reached.  

Caution: May cause under-pressure in the house!

Setting option: Between 0 and 10 °C. The function is 

disabled if set to 0°C. 

25 – Frost protection

If a water reheater with motor-operated valve is installed in 

the system, a frost protection sensor must be fitted to the 

water reheater and the set point must be set to ON.

If no frost protection sensor is installed, the set point must 

be set to OFF. 

Setting option: ON/OFF

26 – Frost protection temperature

If frost protection in item 25 is set to ON, the frost 

protection temperature must be set to the temperature 

where the system should stop and the motor-operated 

valve open completely for the flow of hot water.

Setting option: between 0 and 10°C.

Summary of Contents for ECO 190

Page 1: ...OPERATING INSTRUCTIONS OPTIMA 260 ECO 190 ECO 375...

Page 2: ...TENTS 1 Installation of Optima 100 Design 3 2 Installation of Optima 100 Opus 4 3 Operation 5 4 Data Logger 5 5 Genlog Set Points 9 6 Function 16 7 Maintenance 17 8 Troubleshooting 18 9 Table of Facto...

Page 3: ...point Support point Underneath the control panel there is access for the A Terminal block Connection to main circuit board Fit a 8 x 0 25 mm2 low current cable between the unit and the control panel T...

Page 4: ...able between the ventilation unit print circuit board and the control panel The maximum cable length is 50 m The voltage drop for cable lengths over 50 m is too high and can cause operating errors Che...

Page 5: ...in order to take advantage of the automatic data logging feature The latest version of the Genvex Genlog software can be ordered from Genvex by telephone 45 73532700 1 2 3 4 K3 K5 All Genvex ventilati...

Page 6: ...seful if you want to refer to a certain logging There is an area with grey and white lines at the top of the logging area itself on the screen These lines will be red if relay function is active Hold...

Page 7: ...or monitoring only Data from Control System Set points in control system Opens the following box Here it is possible to retrieve all set points from the microchip or control panel change them and then...

Page 8: ...for the data logger General setup Here you can choose language model as well as folder for the log files For instance it can be a good idea to create a folder for logs under Documents and set up the p...

Page 9: ...ay These days can be filled in individually in the same way as under the example for Monday User menu 01 Temperature Set your desired temperature between 10 and 30 C Item 19 of the Service menu allows...

Page 10: ...or energy consumption or unpleasant indoor climate Setting option between 0 and 100 11 Level 2 Supply air Level 2 is the recommended speed of the system for providing optimal indoor climate It should...

Page 11: ...ith on off bypass e g ECO190 ECO 375 The bypass opens when the temperature reaches the set point in User Menu item 1 the temperature differential set in this menu item Setting option between 1 and 10...

Page 12: ...mper from opening at low outdoor air temperatures and from blowing cold unheated air into the dwelling use this function to configure the lowest outdoor air temperature at which the damper must be clo...

Page 13: ...n 1 25 13 35 Humidity regulating frequency Setting of desired frequency for how often the fan speed may be changed The function is defined as 1 per unit of time When humidity regulation is activated t...

Page 14: ...to maintain a supply temperature of 18 C 41 Reheat PI P P band for the PI controller for the electrical modulating reheater The P band controls the amplification of the controller following a deviati...

Page 15: ...rs Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3 4...

Page 16: ...sion For systems with electrical reheaters the reheater will connect when the temperature has fallen 1 C below the set temperature If the regulation time is set to e g 3 minutes temperature sensorT1 w...

Page 17: ...runs off freely If the condensation drain does not work this could lead to water damage at your home Heat exchanger Inspect the heat exchanger every year If it is dirty remove it and Alu exchanger Was...

Page 18: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Page 19: ...ing 3 C 15 0 C 21 Bypass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduction 0 C 0 10 C 25 Frost protection OFF ON OFF 26 Frost protection...

Page 20: ...t home and in society as a whole a Genvex system actually allows you to recover up to 95 of the heat energy All Genvex systems have energy label A An original Genvex system is built by skilled experie...

Reviews: