background image

 

 

SY-SIX-PX8 | Synergis IX DIN Rail 8 Form C Relay Output Expander | Installation Manual 
Last Updated July 2018 

11

 

DC Power & Encrypted Module Network 

The Output Expander incorporates encrypted RS-485 communications technology, and both module and 
network power are supplied by the N+ and N- terminals. 

NA

N+

N-

NB

Network communications input
from the Controller or previous
module

 

Connection of the communications and DC supply should be performed according to the diagram shown 
above. It is important that the N+ Network Communications Power be 12VDC supplied from an independent 
battery backed power supply unit capable of supplying the required voltage to all devices on the RS-485 
network. 

 

 

Warning:

 

The 12V N+ and N- Communication input must be supplied from only ONE point. Connections from 
more than one 12V supply may cause failure or damage to the Output Expander or device supplying 
network power. 

 

The 330 Ohm EOL (End of Line) resistor provided in the accessory bag MUST be inserted between 
the NA and NB terminals of the FIRST and LAST modules on the RS-485 network. These are the 
modules physically located at the ends of the RS-485 network cabling.   

 

End of Line Resistors: 

330R

330R

First Module on RS-485 Network

Last Module on RS-485 Network

To

Next

Module

From

Previous

Module

NA

N+

N-

NB

NA

N+

N-

NB

 

 

Summary of Contents for Synergis IX SY-SIX-PX8

Page 1: ...Synergis IX DIN Rail 8 Form C Relay Output Expander SY SIX PX8 Installation Manual ...

Page 2: ... state of a product at the time of document s last revision and may not reflect the product at all times in the future In no event shall Genetec be liable to any person or entity with respect to any loss or damage that is incidental to or consequential upon the instructions found in this document or the computer software and hardware products described herein The use of this document is subject to...

Page 3: ...ements 6 Grounding Requirements 7 Safety Grounding 7 Earth Ground Connection 7 Mounting 9 Removal 9 Wiring Diagram 10 DC Power Encrypted Module Network 11 Outputs 12 Outputs 1 to 8 12 Address Configuration 13 LED Indicators 14 Status Indicator 14 Fault Indicator 14 Power Indicator 14 Output Indicators 15 Error Code Indication 16 Error Code Display 16 ...

Page 4: ...lay Output Expander Installation Manual Last Updated July 2018 4 Mechanical Diagram 17 Mechanical Layout 18 Technical Specifications 19 New Zealand and Australia 20 European Standards 21 FCC Compliance Statements 23 Industry Canada Statement 24 ...

Page 5: ...bers of modules to be connected to the RS 485 module network Up to 250 modules can be connected to the Synergis system in any combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module Locking a network prevents the removal substitution or addition of modules to the module network effectively preventing any tampering with ...

Page 6: ...anual Last Updated July 2018 6 Installation Requirements This equipment is to be installed in accordance with The product installation instructions The National Electrical Code ANSI NFPA 70 The Canadian Electrical Code Part I CSA C22 1 The Local Authority Having Jurisdiction AHJ ...

Page 7: ...hould be checked periodically General safety dictates that all metal parts are connected to earth with separate copper wire or wires of the appropriate gauge Earth Ground Connection The DIN Rail enclosure and the DIN Rail modules must be grounded to a single point earth ground For best results a cold water pipe should be used with a pipe wiring clamp If a cold water pipe is not available connect t...

Page 8: ...nclosure s DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings DIN Rail Enclosure Controller Earth Ground Link connection Dialer s Earth Ground Connection Module Network RS 485 N N NA and NB PRT RDM2 DIN PRT PSU DIN V Power Supply Reader Expander PRT PSU DIN Input Expander Output Expander PRT RDM2 DIN Input Expander PRT PSU DIN Input Expander Input Expander V DIN ...

Page 9: ... the Output Expander in a location that will facilitate easy access for wiring It is also recommended that the Output Expander is installed in electrical rooms communication equipment rooms closets or in an accessible area of the ceiling 1 Hook the lower tabs under the bottom edge of the DIN Rail 2 Push the Output Expander against the DIN Rail mount until the upper tab clips over the upper rail Re...

Page 10: ...ramming and will require reference to the module serial number The serial number can be found on the identification sticker on the side of the module Wiring AUX WIRING Min 22AWG Max 16AWG Depends on length and Current consumption For wire cable size a maximum of 5 voltage drop at the terminals of the powered device has to be observed MODULE NETWORK WIRING Recommended Belden 9842 or equivalent 24AW...

Page 11: ...lied from an independent battery backed power supply unit capable of supplying the required voltage to all devices on the RS 485 network Warning The 12V N and N Communication input must be supplied from only ONE point Connections from more than one 12V supply may cause failure or damage to the Output Expander or device supplying network power The 330 Ohm EOL End of Line resistor provided in the ac...

Page 12: ...mation points Outputs 1 to 8 The 8 Outputs each have a FORM C output relay The connection example below shows the control of an external LED indicator 1K5 OHM 12VAUX 0V LED V V NO C NC NO C NC Switching inductive loads that can produce high back EMF voltages or large voltage induced spikes can cause the Output Expander to behave unexpectedly and should be avoided A suitable isolation circuit must ...

Page 13: ...13 Address Configuration The address of the Output Expander is configured via programming and will require entry of the module serial number The serial number can be found on the identification sticker on the product Refer to the Synergis System Controller installation manual for address programming details ...

Page 14: ...on mode enabling the installer to easily identify the module in question Upon either a module update or the identification time period set expiring the module will return to normal operation Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firmware update mode When the ...

Page 15: ...l 8 Form C Relay Output Expander Installation Manual Last Updated July 2018 15 Output Indicators The output indicators will show the status of the outputs State Description Constantly on red Output is ON Constantly off Output is OFF ...

Page 16: ...e is not compatible with the system controller To clear this error update the module using the module update application 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the range set on the system controller restart the module by disconnecting the power 4 Address In Use The Address is already ...

Page 17: ...der PGM Outputs 12VDC Pass Through PGM Outputs 7 8 RS 485 Input PGM Outputs 5 6 PGM Outputs 3 4 12VDC Pass Through PGM Outputs 1 2 12VDC Pass Through 12VDC Pass Through 12VDC Input Status Indicators NC C NO NC C NO V V RELAY 8 RELAY 7 12 VDC OUT NC C NO NC C NO V V RELAY 6 RELAY 5 12 VDC OUT POWER STATUS FAULT 5 6 7 8 OUTPUT 1 2 3 4 N N NA NB V V NO C NC NO C NC 12 VDC IN RS485 NETWORK 12 VDC OUT ...

Page 18: ...r Installation Manual Last Updated July 2018 18 Mechanical Layout The mechanical layout shown below outlines the essential details needed to help ensure the correct installation of the Output Expander 156 8m m 143 5m m 36 4m m 90mm BACK 90mm 156 8mm FRONT 44 1m m ...

Page 19: ...Weight 482g 17oz Temperature Operating UL ULc 0 to 49 C 32 to 120 F EU EN 10 to 55 C 14 to 131 F Storage 10 85 C 14 185 F Humidity 0 93 non condensing indoor use only relative humidity The Total Combined Current refers to the current that will be drawn from the external power supply to supply the Output Expander and any devices connected to the Expander s outputs The Auxiliary outputs are directly...

Page 20: ... Relay Output Expander Installation Manual Last Updated July 2018 20 New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards ...

Page 21: ...s and prevent any potential negative effects on human health and the environment which could otherwise arise from inappropriate waste handling Please contact your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For business users in the European Union If you...

Page 22: ...n 30 seconds the entry delay has expired or another instant is violated the main alarm will be triggered and reported To comply with EN 50131 1 neither Internals Only on Part Set Zone Alarm nor Internals Only on Part Set Tamper Alarm should be selected To comply with EN 50131 1 Single Button Setting should not be selected To comply with EN 50131 1 only one battery can be connected and monitored pe...

Page 23: ...ion which can be deter mined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Changes or modifications not authorized ...

Page 24: ...utput Expander Installation Manual Last Updated July 2018 24 Industry Canada Statement This class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada CAN ICES 3 A NMB 3 A ...

Page 25: ...d the Genetec Logo are trademarks of Genetec Inc and may be registered or pending registration in several jurisdictions Other trademarks used in this document may be trademarks of the manufacturers or vendors of the respective products www genetec com Published July 2018 ...

Reviews: