44-00-0297
SHERLOCK
102/202 REV. 4.1 05-02-15
37
SYSTEM CONFIG MENU
Press
DOWN
arrow button to move to the next option. Set
the Latch Action for all relays The alarm relays can be set to
"NO" (Alarms stay active until reset by a technician) or the
"YES" (Alarm will autoclear when alarm conditons clear)
modes. To change latch method, press
SELECT
button. The
"YES" ("NO") will begin to blink. Press
DOWN
arrow button
to change the blinking "YES" ("NO") to a blinking "NO"
("YES"). Press
SELECT
button to save this entry
Press the
DOWN
arrow button to move to the next option.
Communications Station Number
THIS OPTION IS FOR
REMOTE COMMUNICATIONS AND IS NOT AVAILABLE
ON ALL UNITS AND REQUIRES GENCOM SOFTWARE.
IF YOU DO NOT HAVE THIS FEATURE IGNORE THIS
SCREEN.
To set the baud rate, press the
SELECT
button.
The "1" will begin to blink. You can enter from 1 to 199.
Press the
UP/DOWN
arrow button to change to the desired
value. Press the
SELECT
button to save this entry
Press the
DOWN
arrow button to move to the next option.
Communications Baud Rate
THIS OPTION IS FOR
REMOTE COMMUNICATIONS AND IS NOT AVAILABLE
ON ALL UNITS AND REQUIRES GENCOM SOFTWARE.
IF YOU DO NOT HAVE THIS FEATURE IGNORE THIS
SCREEN.
To set the baud rate, press the
SELECT
button.
The "9.6" will begin to blink. The settings are 9.60, 14.4, 19.2,
and 38.4. Press the
DOWN
arrow button to change to the
desired value. Press the
SELECT
button to save this entry
Press the
DOWN
arrow button to move to the next option.
Press the
SELECT
button to activate the "CLEAR CON-
FIGURES" routine, "YES" starts to blink. Press
DOWN
arrow button. The Control will ask to confirm the confgure
memory clearing. If you do not want to clear the configures,
press
DOWN
arrow button. If you want to continue, press
SELECT
button and then
DOWN
arrow button to start clear-
ing EEPROM, and RAM. After memory clearing and testing,
the "MEMORY OK" message will be shown.
CLEAR ALARM LOG
The alarm log has 10 entries that keeps the most recent alarms.
These entries can be cleared using the following procedure,
Press
SELECT
button to activate the clear alarm log function.
The message "YES" will start to flash, Press
UP/DOWN
arrow
button. The controller will ask you to confirm one more time.
If you do not want to clear the memory, press
UP/DOWN
arrow button else press
SELECT
button to change the blinking
"NO" to a blinking "YES". Press
UP/DOWN
button to begin
the alarm log clearing routine.
Exit this menu and return to DEFAULT SCREEN.
SELECT/
CHANGE
SELECT/
CHANGE
<CFG> CLEAR ALL
CONFIGURES: NO
<CFG> CLEAR ALL
CONFIGURES: NO
<CFG> CLEAR ALL
CONFIGURES: YES
SELECT/
CHANGE
SELECT/
CHANGE
<CFG> CLEAR ALL
ALARM LOGS: NO
<CFG> CLEAR ALL
ALARM LOGS: NO
<CFG> CLEAR ALL
ALARM LOGS: YES
EXIT
<C>ALRM AUTO CLR
AFTER NORMAL:YES
SELECT/
CHANGE
SELECT/
CHANGE
<C>ALRM AUTO CLR
AFTER NORMAL:YES
<C>ALRM AUTO CLR
AFTER NORMAL: NO
<CFG>REMOTE COMM
STATION NO: 1
SELECT/
CHANGE
SELECT/
CHANGE
<CFG>REMOTE COMM
STATION NO: 199
<CFG>REMOTE COMM
STATION NO: 199
<CFG>REMOTE COMM
BAURATE,K: 9.60
SELECT/
CHANGE
SELECT/
CHANGE
<CFG>REMOTE COMM
BAURATE,K: 9.60
<CFG>REMOTE COMM
BAURATE,K: 9.60
Summary of Contents for SHERLOCK 102
Page 3: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 11: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 12 IR SENSOR ...
Page 49: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 50 PAGE FOR FIELD WIRING SHERLOCK SYSTEM ...
Page 51: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 52 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 53: ......