The display is a 2 rows by 20 characters backlighted liquid crystal display. When the Control Module is first powered up, the unit
will display its initialization screens. Thereafter, the reading and the setpoints of each enabled sensor are shown in alterating fash-
ion every three seconds. If no sensor is enabled, the "TIME" screen will be the only screen shown. If the Control is in alarm, the
cause of alarming on each sensor and the alarming level are shown. For those sensors that are in alarm, the correspondent alarm
lights on top of the display will be on.. When in MENUS and if no button is pressed for fifteen minutes, the Control will return to
the DEFAUT SCREEN
REFR LEAK SNR A
READING X PPM
DEFAULT SCREEN
PRESS "EXIT KEY
OR "ALARM CLEAR"
DEFAULT SCREEN / ALARM RESPONSES
*** IN ALARM ***
SNR A OPEN
There are no Sensors enabled
The Control will monitor each sensor according to the alarm settings. When the sensing level exceeds its alarm limit for the
duration of its delay time, the Control will activate the appropriated alarm relays; Level 1 and/or level 2. The alarm will turn
on the internal buzzer and external alarm light, and show the alarm messages. Pressing the "ALARM CLEAR" button on the
front panel will turn off the internal buzzer and the K1 and K3 relays but keep the alarm light lit. The relays (K2 for level 1
and K4 for level 2 and configurable zone isolation alarm relays) can be silenced by pressing the "ALARM CLEAR" button
a second time. The alarm light will also turn off. Do not press the "ALARM CLEAR" button if you do not want to clear
the alarm so the Control will remain in this alarm state until manually cleared or automatically cleared. Once the "ALARM
CLEAR" button has been pressed twice the Control will start new monitoring cycle. If the alarm conditions are not rectified
it will go into alarm again after the alarm delay time. The alarm log can be seen in the alarm menu.
ALARM RESPONSE PROCEDURE
*** IN ALARM ***
RFG SNR A LEVL 1
SENSOR 1 ALARM
TIME XX:XX
5/02/2008
TIME XX:XX
5/02/2008
REFR LEAK SNR B
READING X PPM
Sensor "B" is enabled
Sensor "A" is enabled or Oxygen Sensor is
enabled.
* ALARM SILENCED *
*** IN ALARM ***
RFG SNR A LEVL 2
Sensor is in alarm. Press the "ALARM CLEAR" button once.
*** IN ALARM ***
OXYGEN LOW
REFR LEAK SNR A
SENSOR WARM UP
REFR LEAK SNR B
SENSOR WARM UP
This warm up screen will show for all installed sensors if
a shutdown and restart occurs. The control will remain in
warmup mode for 2 minutes and then switch to default.
OXYGEN SENSOR
READING 20.9 %
Summary of Contents for SHERLOCK 102
Page 3: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 11: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 12 IR SENSOR ...
Page 49: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 50 PAGE FOR FIELD WIRING SHERLOCK SYSTEM ...
Page 51: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 52 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 53: ......