Model S800
4
2.0 System Specifications
2.1
Notice
This Chapter provides detailed specifications for the model S800 Machine Mounted
Methane Monitoring System. The system mechanical, electrical and environmental
specifications present the Model S800 in Technical terms. The unit description is
provided for insertion into other written specifications by architects and engineers.
2.2
System Specifications
Application:
combustible & flammable gas and vapor detection.
Sensor Type:
General Monitors low temperature, catalytic bead, limited diffusion
sensor.
Measuring Range:
0 to 5% Methane gas by volume or 0 to 100%LEL.
Accuracy:
±3% of full scale for gas concentrations up to and including 50% of full
scale. For gas concentrations greater than 50%, the accuracy of the systems will be
±5% of the full scale gas concentration.
Zero Drift:
less than 5% of span per year.
Response Time:
Time to 50% of full scale < 10 seconds with 100%LEL concentration
of Methane applied. Time to 90% of full scale < 30 seconds with 100% LEL
Concentration of Methane Applied.
User Protection:
The Model S800 is MSHA certified (Cert# 32A-23/MS-0),
Commonwealth of Pennsylvania approved (Cert# BFE 1275-96) and warranted for one
year on parts and labor.
AWG Feet Meters
14 7600 2320
16 4800 1460
2.3
Mechanical Specifications
Power Supply:
Weight:
5 lbs 2 oz (2.3 Kg)
Length:
8 inches (20.3 cm)
Height:
3.5 inches (8.9 cm)
Width:
5 inches (12.7 cm)
Summary of Contents for S800
Page 14: ...Model S800 10 Figure 2 Color Coded Wiring Connections ...
Page 28: ...Model S800 7 4 Module Base Assembly Figure 13 Module Base Assembly 24 ...
Page 29: ...Model S800 7 5 Power Supply Assembly Figure 14 Power Supply Assembly 25 ...
Page 30: ...Model S800 7 6 Detector Housing Assembly Figure 15 Detector Housing Assembly 26 ...