Models FL3100H/3101H
61
10.3.3 Electrical Specifications
European Union (EU) Approved Applications:
PSU noise and ripple voltage 1.0Vpp max. The
customer supplied PSU must comply with IEC 61010-1, limiting current to 8A under Fault
conditions, in order to comply with CE Marking requirements.
Nominal supply voltage:
24 VDC
Supply voltage range:
20 to 36 VDC
Maximum supply current:
400 mA during COPM only
Typical current:
80 to 150 mA Depends on relays ETC
Maximum output signal load:
600 Ohms
Output signal range:
0 to 20 mA *
FAULT signal:
0 to 0.2 mA *
COPM fault signal:
2.0
0.2 mA *
Ready signal:
4.0
0.2 mA
IR only signal (FL3100H only):
8.0
0.2 mA
UV only signal (FL3100H only):
12.0
0.2 mA
WARN signal:
16.0
0.2 mA
ALARM signal:
20.0
0.2 mA
Relay Contact Ratings:
North American Approved Applications:
SPDT, 8A, @ 250VAC, or 8A @ 30
VDC resistive max.
European Union (EU) Approved
Applications:
SPDT, 8A 30V
RMS/42.4V Peak, 8A @ 30 VDC,
resistive max.
RS-485 Output:
Modbus RTU
128 units in series max.
(247 units with repeaters)
Baud Rate: 2400, 4800, 9600 or 19200
BPS
Optional: Dual Modbus RTU
Communications available
(See Section 3.3 Terminal Connections,
for Alarm Output Connections)
HART:
Fully HART Foundation compliant. See
separate HART manual for use of
HART.
HART Impedance:
R
X
= _50 K C
X
= 5 nF
AMS Aware:
Certified by AMS
RFI/EMI Protection:
Complies with EN 50130-4, EN 61000-
6-4
Status Indicator:
Two LEDs indicate status, fault and
alarm conditions
* Normal non-HART version. See analog output Section 3.3.6 for other currents.
10.3.4 Environmental Specifications
Operating temperature range:
-40°F to 185°F (-40°C to 85°C)
Storage temperature range:
-40°F to 185°F (-40°C to 85°C)
Humidity range:
0 to 100% RH non-condensing
Summary of Contents for FL3101H
Page 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Page 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Page 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Page 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...