Models FL3100H/3101H
19
3.3.1 Terminal
Connections
All wire connections are made through the base entries to the terminal block (Figure 19).
The terminal block accepts 14 AWG to 22 AWG (2.1 to 0.3 mm
2
) stranded or solid core
wire. Each wire should be stripped to .25 in (.64 cm). To connect the wire to the terminal
block, insert the conductor into the connection space as shown in Figure 19 and tighten
the corresponding screw terminal. There are twenty terminal connections. The following
pages contain descriptions and specifications for each connection.
WARNING:
Relay contacts must be protected against transient and over-voltage
conditions (Figure 20).
Figure 20: Protection Circuits for Relay Contacts
3.3.2 Terminal Block TB2 – Alarm Relay Connections
TB2
Position
Alarm
Relays
Relay Contact
(De-Energized)
Relay Contact
(Energized)
2 C
Common
Common
3
1
Normally Closed
Normally Open
4
2
Normally Open
Normally Closed
Table 1: TB2 Alarm Relay Connections
These connections are for the SPDT ALARM relay. The ALARM output is time delayed
for 2, 4, 8 or 10 seconds. This time delay can be set by Modbus, HART, or by Dipswitch.
The ALARM output can be normally energized or normally de-energized, latching or
non-latching, and these options are also set via can be set by Modbus, HART, or by
Dipswitch (Section 4.4). For all relay connections see Figure 20.
H
H
H
H
Summary of Contents for FL3101H
Page 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Page 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Page 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Page 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...