Model 4802A
28
5.4.3 A2 Alarm Options
Next, the
A2
LED will be flashing while the Energized/De-Energized option is displayed
(Figure 50). The display will indicate the current selection, (
En
or
dE
). Press the
Mode/Select
Switch to toggle the selection.
De-Energized
is the factory default for this
selection.
Figure 50 – A2 Energized/De-Energized Alarm Option
The
A2
LED on the front panel will be flashing while the latching/non-latching option is
displayed (Figure 51). The display will indicate the current selection, (
nL
or
LA
). Press
the
Mode/Select
Switch to toggle the selection.
Latching
is the factory default for this
selection.
Figure 51 – A2 Latching/Non-Latching Alarm Option