Model 4802A
23
When the
CAL LED
is on steady, release the Mode/Select switch. The display will show
flashing bars (
- -
) for about ten seconds, then an
AC
indication on the display. The unit
is now in the Calibration Mode (Figure 43).
Figure 43 – AC Display During CAL Mode
Apply the gas by opening the valve on the cylinder and the ON/OFF valve and watch the
display change from
AC
to
CP
as the sensor sees gas (Figure 44). If the display does
not change from
AC
to
CP
after six minutes, the Model 4802A will return to
normal operation.
Figure 44 – CP Display During CAL Mode