Electrical Connections
20
Installation Manual for Generac PWRCell Inverter
Connecting CTs to the Inverter
1.
. Connect CT leads to RJ-45 Break
-
out Adapter’s (M) push terminals according to the
label on the breakout adapter.
NOTE:
Use yellow lead for CTx+ and use green lead for
CTx-.
Figure 5-8. RJ-45 Breakout Adapter
NOTE:
RJ-45 Breakout Adapter is included in the
Generac PWRcell Kit.
NOTE:
If the RJ-45 Breakout Adapter is not available,
the CT leads can be wired to a Category 5 (Cat 5) cable.
Use
to wire CTs directly to stripped Cat 5 wire.
2.
See
. Connect Cat 5 cable to CT input
jack (H).
NOTE:
The connection between the RJ-45 breakout
adapter and the inverter is made using a widely available
installer supplied Cat 5 style cable.
• CT input jack is a double-stacked RJ-45 jack.
• Either the top or bottom port may be used.
• Both jacks may be used when multiple sets of
CTs are required.
:
Figure 5-9. Accessory Ports
NOTE:
When setting an ESS Grid Usage Mode other
than the default unrestricted mode, attach the label
packaged with the CTs to the inverter.
Connecting Multiple Sets of CTs
When installing CTs, local factors may require multiple
sets of CTs to fully measure the utility power being sent
to the building.
For 4-wire, 120/240 VAC, split-phase service:
•
Use two pairs of CTs to measure the service. Use
each pair of CTs to measure a pair of service
conductors/feeders within the main panel.
•
Use both RJ-45 jacks with two Cat 5 cables.
•
Connect CT1 from both cables to the same phase
and CT2 cable from both cables to the second
phase.
•
See
Table 5-9: Multiple CT Connection
. Connect
Cat 5 cables from the adapters into the two CT
accessory ports.
NOTE:
Make sure to use the same pinout and
connections.
Table 5-8. CT RJ-45 Pinout
Pin
Wire Color
(T-568A)
Wire Color
(T-568B)
Value
1
White / Green
White / Orange
CT3+
2
Green
Orange
CT3-
3
White / Orange
White / Green
CT2+
4
Blue
Blue
CT1+
5
White / Blue
White / Blue
CT1-
6
Orange
Green
CT2-
7
White / Brown
White / Brown
Not Used
8
Brown
Brown
Not Used
NA NA CT
2
‒
CT
1
‒
CT1+ CT2+ CT
3
‒
CT3+
010222
M
H
Current Transformers (CTs) accessory port (RJ-45)
I
Automatic Transfer Switches (ATS) accessory port
(RJ-45)
J
REbus Beacon Port (USB-B)
K
Authorized Generac Personnel Only
L
STOP Terminals
Table 5-9. Multiple CT Connection
CT
Service
Phase and
Wire Adapter
Adapter Adapter
Pins
CT Port
Row
Values
1-1
L1-1
1
4 and 5
Front Port
1-2
L2-1
1
3 and 6
Front Port
2-1
L1-2
2
4 and 5
Back Port
2-2
L2-2
2
3 and 6
Back Port
AT
S
CT
s
010001
H
I
J
K
L