Installing PWRcell Inverter
12
Installation Manual for Generac PWRcell Inverter
Mounting the Inverter
1.
Verify mounting location adheres to the following
requirements:
•
Location must meet all PWRcell inverter
requirements listed in Section 3 of this manual.See
for more information.
•
Inverter must be mounted upright on a vertical wall.
•
Never obstruct intake or exhaust vents.
•
Never allow water to enter intake or exhaust vents.
•
Observe all mounting clearances. See
Inverter Dimensions and Mounting Clearances
.
2.
Secure mounting bracket mounting surface
through mounting holes.
•
Fasteners must adequately secure the 70.9 lbs
(32.1 kg) inverter weight to the wall.
•
Fasteners must be suitable for the mounting
surface.
•
Fasteners must engage at least two studs or other
structural members.
•
Mounting bracket has clearance holes for 1/4”
fasteners with slots to accommodate different stud
spacings.
3.
See
. Insert mounting bracket tabs (A)
into inverter body slot (B).
NOTE:
is for illustration purposes only.
Figure 4-3. Mounting Inverter onto Bracket
4.
See
. Secure the bottom of the inverter
to wall with two fasteners through mounting holes
(C). Holes are spaced at 11 1/4 in from each other.
Use anchors or blocking as needed.
Figure 4-4. Mounting Holes
(000641a)
CAUTION
Equipment damage. Mount inverter to a strong, stable surface.
Never mount to drywall, plaster, or other non-structural wall
treatments. Failure to mount inverter to a strong, stable surface
could result in equipment or property damage.